Reactive Factor Controller CX plus
11
Solution:
Correct the connection, execute the “Automatic initialisation (AI)” or add 180° to resp. subtract
180° from the set phase correction angle (SETUP/206) (new angle < 360°).
Please observe the separate notes at the end of the chapter for the setting of the phase
correction angle.
Also see chapter
“
Automatic initialisation
”
5)
Incorrect “
COS PHI
“ is displayed
incorrect connection
Incorrect phase between measuring voltage and current. Please check the connection of measuring
voltage and current (phase, polarity).
Possible causes:
The set phase correction angle does not correspond to the connection of measuring voltage and
current.
Solution:
Correct the connection, execute the “Automatic initialisation (AI)” or manually set the phase
correction angle correctly.
Measuring voltage or current has been connected at a twisted angle of 180° from the direction of
connection (U2 / U1 instead of U1 / U2 resp. S2 / S1 instead of S1 / S2).
Solution:
Correct the connection, execute the
“Automatic initialisation (AI)” or add 180° to resp. subtract
180° from the set phase correction angle (SETUP/206) (new angle < 360°).
Please observe the separate notes at the end of the chapter for the setting of the phase
correction angle.
Also see chapter
“
Automatic initialisation
“
6)
Display
“
AI Abrt
”
The “Automatic initialisation” (AI) was cancelled with error.
Possible causes:
Heavy load fluctuations during the “Automatic initialisation (AI)”
Solution:
Restart the “Automatic initialisation (AI)”, when the mains is steadier. The measuring current
was too small.
The current transformer ratio may be too large.
Solution:
Check if the selected current transformer corresponds to the system and change it, if
necessary. Restart the “Automatic initialisation (AI)”.