Technical documentation
Rev. 02
Reactive Factor Controller CX plus
29
1.00
i
1.00
i
INFO
1.00
i
MANUAL
1.00
i
SETUP
100
SETUP
Un
400
V SETUP
Setting of the nominal voltage
Un = phase voltage
. This value is
required for the monitoring of the
voltage tolerance. The step sizes saved
in the step database also refer to the
nominal voltage.
1.00
i
ALARM
Ct
50
SETUP
Entry of current transformer factor
e.g. 250/5 = 50
Pt
1
SETUP
Entry of voltage transformer factor
(if no transformer is used, value = 1)
Ai
no
SETUP
"Yes": The controller performs an
identification of the phase (connection
of measuring voltage and current) and
of the occupied and non-occupied
switching outputs (AUTO-INIT).
PFC
On
SETUP
"ON" control ON,
"OFF" control OFF,
"HOLD" control is stopped
CP1
1
SETUP
Target COS
1 of the control