Reactive Factor Controller CX plus
68
“YES”
= HIGH active
“NO”
= LOW active
Function:
If the digital input is activated, an active I-
LOW alarm is suppressed. “
YES
” is shown on the status
display for the I-LOW alarm suppression (SETUP/519).
If the digital input is no longer activated, the suppression is deactivated. An active I-LOW alarm is
signalled now (display and alarm relay).
“
NO
” is shown on the status display of the I-LOW alarm suppression (SETUP/519).
NOTE:
If an active I-LOW alarm is signalled and if the digital input is activated for suppression, the
alarm message is only reset after 15 s. The AUTO symbol is not displayed again until the set
switching time has run out, provided that the control is not switched off.
NOTE:
If an active I-LOW alarm is being suppressed at the moment and if the digital input is no longer
activated, the alarm is not signalled until the delay time of 60 s has run out.
NOTE:
If the delay time has not run out yet and if the digital input is activated again, an active I-LOW
alarm is suppressed immediately. If the digital input is no longer activated, the delay time is restarted
(60 s). The I-LOW alarm is signalled after the delay time has run out.