Reactive Factor Controller CX plus
62
NO = LOW active
YES = HIGH active
No
display notification “
NT
”, control
does not work with target COS-
PHI, even though the digital
input is activated.
The function of the digital
input is switched to
“Suppression of I-LOW
alarm
”.
Logic digital input is set
incorrectly.
Check the setting for the
switching between
functions of the digital input
(SETUP/518), switch to
“NO”, if necessary.
Check the setting of logic
digital input (SETUP/511),
switch to logic, if necessary:
NO = LOW active
YES = HIGH active