7.4.3
Menù “I” – Inputs and outputs
7.4.4
Menu “C” – Commands
(*) IMPORTANT:
programming C.002=1 the S2022 reload the default setup.
I/Os
Digital inputs
I.000
I.001
6
6
600
601
Dig inp 1 cnf
Dig inp 2 cfg
0 NONE
1 INCREASE
2 DECREASE
3 FCR Remote enabling
4 52G: Pa DROOP
5 52G: Pa PF reg.
6 52G: PaVAR reg.
-
-
1
2
Name IPA
Descrip�on
[U.M.]
Default Max
Notes, values
0
Digital outputs
I.100
4
603
Dig out 1 cnf
0 NONE
1 FAULT
2 NOT FAULT
3 LIMIT
4 NO LIMIT
-
3
0
RS485
I.400
4
604
RS485 config
0 custom protocol
1 Modbus RTU 8N1
2 Modbus RTU 8E1
3 Modbus RTU 8O1
4 Modbus RTU 8N2
-
1
0
I.401
5
605
RS485 bitrate
0 4800
1 9600
2 19200
3 38400
4 57600
5 115200
-
3
0
I.402
247
606
RS485 node ID
-
1
1
I.404
0,100
607
RS485 delay
s
0,005
0,000
0
I.002
6
602
Dig inp 3 cfg
-
5
0
Min
COMMANDS
U�lity commands
C.000
C.002
1
1
1600
1601
Params save
Default Params
reload
8192=100%
(*)
-
-
0
0
Name IPA
Descrip�on
[U.M.]
Default Max
Notes, values
0
0
C.200
8192
1602 Test step
-
0
-8192
0= Field I ref
1= Generator V ref
2= Generator PF ref
3= Generator VAR ref
C.201
3
1603 Test step type
-
1
0
Min
BELTRAME
CENTRO SERVIZI ENERGIA