11
3. DEVICE CONNECTIONS
3.1 Input/Output power connec�on / rated data
Required Qualifica�on
Personnel involved in installa�on work and commissioning of the S2022 must be familiar,
specially instructed and informed about the residual danger areas according to the regula�ons
currently in force.
Only specially instructed personnel must carry out maintenance and repair work.
3.2 Device connec�ons: CN2 Interface
CN2 picture:
* IMPORTANT
: S2022 allows the sudden applica�on of the full power supply voltage (230V)
Terminal designa�on
(CN1, FX1 AND FX2)
Auxiliary power supply
(CN1)
ADC Input voltage
12÷35 Vdc
+ , -
Auxiliary power supply
(*)
(FX1)
Input voltage
mono/three phase
DC Input
Rated 230 Vac - (max 300 Vac)
0÷500 Hz
0÷300 Vdc
L1, L2, L3
Terminals
Signal
Specifica�ons
Measurements inputs
(FX1)
(FX2)
Generator voltage
Generator current
0÷115Vrms
0÷490 Vrms (with bridge between 115V and B)
0÷300 Vdc
0-115-B-490
TA s1 – TA s2
Excita�on output (Field)
(FX1)
Generator voltage
Generator current
300Vdc max
0÷10 A (20 A per 10 s)
-, +
Terminal
designa�on
Modbus RTU and proprietary
protocols
half duplex
Not isolated
from power
supply
Communica�on
Descrip�on
Diagram
BELTRAME
CENTRO SERVIZI ENERGIA
LINK +
LINK -
GND
S2022
CN2
5
5V
1K
1K
120
4
2
1
Ω
Ω
Ω
Summary of Contents for S 2022