6.5 Digital reference adjustment by calibrator (Up/Down)
In AVR mode, by programmed digital inputs (I.000=1 increase, I.001=2 decrease) on CN3 connector, it is possible to adjust the nominal
voltage set point in a range between -r.010% and +r.010%. The same func�on is available in FCR mode, in this case the UP/DOWN input is
influencing the excita�on current.
A�er closing of 52G (programmed as I.002=5 (Pa PF regula�on)), the “increase” and “decrease” commands increase or decrease the
Power Factor value.
A�er closing of 52G (programmed as I.002=6 (Pa VAR regula�on)), the “increase” and “decrease” commands increase or decrease
the Reac�ve Power value.
6.6 Digital reference adjustment by analog inputs
As above, using the analog inputs (Poten�ometer or ±5Vdc) on CN3 connector, it is possible to adjust the set point in a range between
-r.011% and +r.011%.
AVR/FCR
PF/VAR
AVR/FCR
PF/VAR
As default r.010 is programmed to 0%, this means the Up/Down func�on is disabled.
Set the desired adjustment range to ac�vate the func�on.
As default r.011 is programmed to 0%, this means the Up/Down func�on is disabled. Set the
desired adjustment range to ac�vate the func�on.
IT IS RECOMMENDED TO DO NOT USE SIMULTANEOUSLY ANALOG AND DIGITAL INPUTS FOR
SET POINTS MODIFICATIONS.
BELTRAME
CENTRO SERVIZI ENERGIA
+ r.010
- r.010
Reference
P.100
r.000
+ r.410
- r.410
Reference
r.400
r.401
+ r.011
- r.011
Reference
P.100
r.000
+ r.411
- r.411
Reference
r.400
r.401