![Beltrame S 2022 User Manual Download Page 17](http://html1.mh-extra.com/html/beltrame/s-2022/s-2022_user-manual_2730735017.webp)
16
Field Flashing OFF (disabled):
Field Flashing and self-excita�on procedure is influenced also by the Keep Alive func�on. The
“keep alive”
feature allows to maintain a
minimum excita�on current even when the Generator frequency drops below the minimum (P.130). The minimum excita�on current value
can be adjusted using parament P.250; this se�ng must be done based on the power source (set up to 0 if the power is from PMG or
auxiliary). With “keep alive” enabled (P.250>0), the S2022 will try to keep a minimum excita�on current during the start-up (and during the
shu�ng down). As default P.250 is adjusted to 5. This means that the S2022, during the start-up (and shut-down), will try to keep the
excita�on current to 5% of the rated excita�on current (P.000). Once the frequency will be higher the P.130 (Generator minimum frequency),
the AVR will leave the “keep alive” area and will enter in the V ramp area.
In case the AVR is powered with a PMG or with an external power source the “Keep Alive” func�on has to be disabled (set P.250=0).
With P.250=0 also the Field Flashing is disabled, does not ma�er the bridge posi�on described above.
Above screenshot shows the Field Flashing and the Keep Alive func�ons effects during generator star�ng up and shu�ng down. Once the
frequency drops below P.130 the AVR ac�vates the keep alive func�on and works in order to maintain the excita�on current to the P.250
keep alive se�ng (in this case 5%).
Parameter
Description (short)
Description
P.250
P.130
KeepAlive min I
Gen. V/f min freq
% of the rated exc current (P.000) from 0Hz to P.130 Hz
Generator minimum frequency (Hz)
BELTRAME
CENTRO SERVIZI ENERGIA
Summary of Contents for S 2022
Page 1: ...Rev 4 0 BELTRAME CENTRO SERVIZI ENERGIA ...
Page 2: ......
Page 44: ...43 BELTRAME CENTRO SERVIZI ENERGIA ...