12
3.3 Device connec�ons: CN3 I/O control signals
CN3 picture:
Terminal
designa�on
3 programmable digital inputs
• 4mA max current
• Up / Down /
programmable func�on
• AVR/FCR/PF/VAR mode
CN3 Digital inputs
Descrip�on
Diagram
N.1 programmable digital
output
Max Load 65mA 24Vdc
CN3 Digital outputs
Analog input signals to
remote adjust the setpoint
The voltage
analog input
is not isolated
from power
supply
2x Analog inputs
Analog input: ± 5V
Poten�ometer input: 1kohm
Ω
BELTRAME
CENTRO SERVIZI ENERGIA
S2022 CN3
COM
Increase
Decrease
52G
Analog in
Poten�ometer
Out (E)
Out (C)
S2022 CN3
COM
Increase
Decrease
52G
Analog in
Poten�ometer
+24Vdc
GND
S2022 CN3
COM
Increase
Decrease
52G
Analog in
Poten�ometer
+24Vdc
GND
S2022 CN3
COM
Increase
Decrease
52G
±
5V
Analog in
Poten�ometer
Out (E)
Out (C)
Out (E)
Out (C)
Out (E)
Out (C)
S2022 CN3
COM
Increase
Decrease
1k
52G
Analog in
Poten�ometer
Out (E)
Out (C)