23
6.3 Power Factor regula�on (PF)
The AVR controls in automa�c mode the power factor at generator terminals. The PF func�on is ac�ve when P300= 1, and I002= 5; once the
52G digital input (generator in parallel) is closed, the PF func�on starts to work. Generator current reading is necessary to use this func�on.
Be aware of the correct PF reading.
6.4 Reac�ve power regula�on (VAR)
The AVR controls in automa�c mode the reac�ve power at generator terminals. The VAR func�on is ac�ve when P300= 1, and I002= 6; once
the 52G digital input (generator in parallel) is closed, the VAR func�on starts to work. Generator current reading is necessary to use this
func�on. Be aware of the correct VAR readin
Parameter
Description
Note
r.400
r.402
r.450
r.451
r.410
r.411
r.412
Generator PF digital ref
Ramp slope
PF/VAR Reg KP
PF/VAR Reg TI
Delta Ref Calibrator
Delta Ref analog
Delta ramp slope
Parameter
Description
Note
r.401
r.402
r.450
r.451
r.410
r.411
r.412
Generator VAR digital ref
% compared to P.100 xP.110
Ramp slope
PF/VAR Reg KP
PF/VAR Reg TI
Delta Ref Calibrator
Delta Ref analog
Delta ramp slope
BELTRAME
CENTRO SERVIZI ENERGIA
Q+ (var)
Q-
P (w)
Motor
Generator
r.400
r.400
Q+ (var)
Q-
P (w)
Motor
Generator
r.401
r.401
Summary of Contents for S 2022
Page 1: ...Rev 4 0 BELTRAME CENTRO SERVIZI ENERGIA ...
Page 2: ......
Page 44: ...43 BELTRAME CENTRO SERVIZI ENERGIA ...