background image

When enabled, ‘t-rE5Et’ allows an operator to reset
the BA558E total display to zero by operating the

 and

 

 push buttons simultaneously for at least

two seconds.    To check the status of ‘t-rE5Et’
select 'LoC.r5Et'' from the configuration menu and
press

 

P.

   Using the 

 or 

 button select ‘t-rE5Et’

and  press  

P

  which  will  reveal  if  the  function  is

turned 'on' or 'oFF'.   Operating the 

 or 

 button

will toggle the display between the two conditions.
When set as required  pressing the

 

E

 

button  will

enter   the   selection   and   return   the   display   to   the
‘t-rE5Et’  sub-function.    The  remote  reset  facility
described  in  section  3.2  of  this  manual  is  not
affected by the status of this local reset function.

When  enabled,  ‘Gt-rE5Et’  allows  an  operator  to
reset the BA558E grand total to zero by operating
the  

E

 and

 

 push buttons simultaneously for at

least ten seconds.  To check the status of ‘t-rE5Et’
select 'LoC.r5Et'' from the configuration menu and
press

 

P.

   Using  the  

 or  

 button  select

‘Gt-rE5Et’  and  press  

P

  which  will  reveal  if  the

function is turned 'on' or 'oFF'.   Operating the 

 or

 button will toggle the display between the two

conditions.  When set as required pressing the

 

E

button  will  enter  the  selection  and  return  the
display to the  ‘Gt-rE5Et’ sub-function.

5.18  Security code:  ‘CodE’

Access to the instrument configuration menu may
be protected  by a  four  digit  security  code  which
must be entered to gain access.   New instruments
are configured with the default security code 0000
which  allows  unrestricted  access  to  all
configuration functions. 

To enter a new security code select 'CodE' from
the  configuration  menu  and  press

 

P

 which  will

cause  the  Rate  Totaliser  to  display  the  existing
security code with one digit flashing.  The flashing
digit  can  be  adjusted  using  the  

 and

 

 push

buttons,  when  set  as  required  operating  the  

P

button will transfer control to the next digit.   When
all the digits have been adjusted press

 

E

 to return

to  the  ‘CodE’  prompt  in  the  configuration  menu.
The revised security code will be activated when
the Rate Totaliser is returned to the display mode.
Please contact BEKA associates sales department
if the security code is lost.

5.19  Reset to factory defaults:  ‘r5Et’

This function enables the Rate Totaliser and the
lineariser  to  be  quickly  returned  to  the  factory
default  configurations  shown  in  sections  5.2  and
6.5

To  reset  the  Rate  Totaliser  or  lineariser  select
‘r5Et’ from the configuration menu and press 

P

, the

Rate Totaliser will display one of the reset options
‘ConF’ or ‘LtAb’.   

‘ConF’

Resets the Rate Totaliser to defaults

‘LtAb’

Resets the lineariser to defaults

Using the 

 or 

 push button select the required

sub-function and press  

P.

   To prevent accidental

resetting  the  request  must  be  confirmed  by
entering ‘5urE’.   Using the 

 button set the first

flashing digit to ‘5’ and press  

P

 to transfer control

to  the  second  digit  which  should  be  set  to  ‘u’.
When  ‘5urE’  has  been  entered  pressing  the  

E

button will reset the selected configuration menus
and return the display to the ‘r5Et’ function in the
configuration menu. 

5.20  Over-range

Numerical over-range of the rate or total displays is
indicated by all the digits displaying ‘9’ and all the
decimal points flashing. 

When  the  total  display  exceeds  99999999  or
-9999999 it will not automatically roll-over to zero
and  continue  counting,  but  the  grand  total  will
continue to count.   If it is likely that the total will
exceeds  99999999  or  -9999999  the  grand  total,
which  has  a  capacity  of  10

16

 and  –10

15

 counts,

should be reset to zero at the start of the operation.

If the total display exceeds 99999999 or -9999999
when the BA558E has been configured for          bi-
directional flow, the total display will be locked and
will not record flow in the opposite direction to the
over-range, although the grand total will continue
to function.

17

Summary of Contents for BA558E

Page 1: ...Issue 3 4th July 2014 BA558E General Purpose 4 20mA loop powered panel mounting Rate Totaliser Issue 3...

Page 2: ...ion using external current source 6 1 1 Example Adding break points to a new Rate Totaliser 6 2 Calibration using internal reference 6 2 1 Example Adding break points to a new Rate Totaliser 6 3 Error...

Page 3: ...vated Loading message displayed Configuration message displayed Model and firmware version displayed The BA558E Rate Totaliser starts functioning using configuration information stored in the instrume...

Page 4: ...mode Operating the or button will toggle the display to CLr YE5 with YE5 flashing operating the E button will then clear the grand total and Gt CLrd will be displayed to confirm the operation The ins...

Page 5: ...nce of less than 1k as shown in Fig 2 Note The negative reset terminal RS2 is internally connected to the negative 4 20mA input terminal 3 The total display may also be reset to zero by operating the...

Page 6: ...3 Installation Procedure a Cut the specified aperture in the panel To achieve an IP66 seal between the instrument enclosure and the instrument panel the aperture must have the tighter tolerances spec...

Page 7: ...as an accessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it...

Page 8: ...lay at 20mA are adjustable although for flow application the display at 4mA is usually zero The position of the decimal point in the rate display is defined by the dP function To simplify calibration...

Page 9: ...onfiguration Access code CodE 0000 Function FunC 5td Linear Rate display at 4mA Zero 0 00 Rate display at 20mA 5PAn 100 00 Resolution rE5n 1 digit P button in display mode C P Local reset of total t r...

Page 10: ...s operated in the display mode Select PC of 4 20mA input 4 20 Current in mA Note PC is not available with lineariser See section 5 14 Display Summary of function 5CALE t Total scale factor Defines the...

Page 11: ...ntains two sub functions Select ConF Returns instrument to default configuration shown in section 5 2 LtAb Returns lineariser to defaults shown in section 6 5 Both instructions must be confirmed by en...

Page 12: ...12...

Page 13: ...arity with bi directional flow Use of the lineariser is described in section 6 of this instruction manual 5 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 14: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 15: ...s been activated see section 5 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 16: ...he or button When the required total scale factor has been set press E to enter the number and return to the 5CALE t prompt in the configuration menu 5 16 Clip off CLiP oFF To prevent totalisation of...

Page 17: ...g the P button will transfer control to the next digit When all the digits have been adjusted press E to return to the CodE prompt in the configuration menu The revised security code will be activated...

Page 18: ...Lineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is require...

Page 19: ...19...

Page 20: ...llowing break point 6 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 21: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 22: ...er the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or butt...

Page 23: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 24: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 25: ...tly the following table may help to identify the cause of the failure Symptom Cause Check No display and no voltage between terminals 1 3 or 12 3 if optional backlight is loop powered No power supply...

Page 26: ...New Rate Totalisers are supplied with the tag or application information specified when ordered thermally printed onto the rear panel adjacent to the terminals This tag information is not visible fro...

Page 27: ...sed and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 12 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switch any...

Page 28: ...28...

Page 29: ...ivated when the selected display rate or total equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally cl...

Page 30: ...y pressing the or button followed by the E button to return to the alarm menu 9 3 7 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 31: ...ate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs are...

Page 32: ...to the display mode Fig 15 Setpoint adjustment from the display mode To adjust an alarm setpoint select 5Px1 or 5Px2 and press P which will reveal the current setting Each digit of the setpoint may b...

Page 33: ...backlight 9 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the Rate Totaliser s 4 20mA input as shown in Fig 17 which increases the maximum Rate Totalis...

Reviews: