background image

e.g.  A Rate Totaliser with a high alarm set at 9000
and an alarm delay of 30 seconds will perform as
follows:

The alarm annunciator will start to flash when an
increasing rate display equals 9000, but the alarm
output  will  not  be  activated  until  the  alarm
condition has existed continuously for 30 seconds.
When  the  alarm  output  is  activated,  the  alarm
annunciator  will  stop  flashing  and  become
permanently activated.

If  the  ‘FL5H’  function,  which  flashes  the  Rate
Totaliser display when an alarm occurs, has been
enabled, it will not start to function until the alarm
output is activated.  
See section 9.3.11

9.3.10  Alarm silence time:   5iL

This function is primarily intended for use in small
installations  where  the  alarm  output  directly
operates an alarm annunciator such as a sounder
or beacon.  When the alarm silence time, which is
adjustable  between  0  and  3600  seconds  in  1
second increments, is set to any figure other than
zero, the 

P

 push-button becomes an alarm accept

button.   After an alarm has occurred, operating the

P

 button will cause the alarm output to revert to the

non-alarm  condition  for  the  programmed  alarm
silence time.  If the alarm condition still exists at
the end of the silence time, the alarm output will be
reactivated.    During  the  silence  time  the  Rate
Totaliser  alarm  annunciator  will  flash  until  the
silence time expires or the alarm is cleared. 

If  the  ‘FL5H’  function,  which  flashes  the  Rate
Totaliser display when an alarm occurs has been
enabled,  it  will  only  function  when  the  alarm
output  is  activated,  not  during  the  silence  time.
See section 9.3.11

To adjust the alarm silence time select '5iL' from
the alarm configuration menu and press  

P

 which

will reveal the existing silence time.   The flashing
digit of the silence time can be adjusted using the

 and 

 push buttons, and the 

P

 button to move

control  to  the  other  digits.    When  the  required
silence time has been entered press 

E

 

to return to

the alarm menu.

9.3.11 Flash display when alarm occurs

 

‘FL5H’

In addition to the two alarm annunciators on the
Rate  Totaliser  display  which  show  the  status  of
both alarms, this function provides an even more
conspicuous indication that an alarm condition has
occurred.    

When enabled, the rate or total display depending
upon  which  has  caused  the  alarm,  alternates
between   the   numerical   value   and   the   alarm

reference, ‘ALr1’ or ‘ALr2’ when the alarm output is
activated.  If both alarm outputs are activated by
one  variable,  the  display  alternates  between  the
numerical value and ‘Alr1-2’.

To  enable  or  disable  the  function  select  'FL5H'
from the alarm menu and press 

P

 which will reveal

the current setting.  The function can be changed
by pressing the 

 or 

 button followed by the  

E

button to return to the alarm menu.

9.3.12  Access setpoint in display mode:  

         AC5P

This function enables a separate menu providing
access  to  the  alarm  setpoints  from  the  display
mode  by  simultaneously  operating  the  

P

 and  

push buttons.  An operator can therefore adjust the
alarm setpoints without having access to the Rate
Totaliser  configuration  menu.    Protection  against
accidental  adjustment  of  the  setpoints  when  the
Rate Totaliser is in the display mode is provided by
a separate security code.

This direct setpoint access menu is enabled and
the separate security code entered from the 'AC5P'
function in the alarm configuration menu as shown
in Fig 14.  To change the menu parameters select
'AC5P' from the configuration menu and press  

P

which will display the enable prompt 'EnbL'.  Press

P

 again to reveal if the direct access menu is 'on'

or 'oFF'.  The 

 or 

 button will toggle the display

between the two conditions.  

If  'oFF'  is  selected,  the  operator  will  not  have
access  to  the  setpoints  from  the  display  mode.
Return to the 'AC5P' prompt in the main menu by
pressing

 

E

 twice.  

If  'on'  is  selected,  the  operator  will  have  direct
access  to  the  alarm  setpoints  from  the  display
mode via a separate optional security code.   To
define this four digit security code press 

P

 to return

to the 'Enbl' prompt followed by the 

 or 

 button

to  select  the  access  code  prompt  'ACCd'.
Pressing  

P

 

will  reveal  the  current  security  code.

Each  digit  of  the  code  may  be  changed  by
operating the 

 and 

 push buttons, and the  

P

button to move control to the next digit.  When the
required code has been entered, press 

E

 twice to

return  to  the  'AC5P'  prompt  in  the  configuration
menu.

Default  code  0000  will  disable  the  security  code
allowing  direct  access  to  the  setpoints  in  the
display  mode  by  pressing  the

 

P

 

and  

 buttons

simultaneously.  Unless otherwise requested new
instruments  with  alarms  are  supplied  with  this
function  disabled  and  the  security  code  set  to
0000.

31

Summary of Contents for BA558E

Page 1: ...Issue 3 4th July 2014 BA558E General Purpose 4 20mA loop powered panel mounting Rate Totaliser Issue 3...

Page 2: ...ion using external current source 6 1 1 Example Adding break points to a new Rate Totaliser 6 2 Calibration using internal reference 6 2 1 Example Adding break points to a new Rate Totaliser 6 3 Error...

Page 3: ...vated Loading message displayed Configuration message displayed Model and firmware version displayed The BA558E Rate Totaliser starts functioning using configuration information stored in the instrume...

Page 4: ...mode Operating the or button will toggle the display to CLr YE5 with YE5 flashing operating the E button will then clear the grand total and Gt CLrd will be displayed to confirm the operation The ins...

Page 5: ...nce of less than 1k as shown in Fig 2 Note The negative reset terminal RS2 is internally connected to the negative 4 20mA input terminal 3 The total display may also be reset to zero by operating the...

Page 6: ...3 Installation Procedure a Cut the specified aperture in the panel To achieve an IP66 seal between the instrument enclosure and the instrument panel the aperture must have the tighter tolerances spec...

Page 7: ...as an accessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it...

Page 8: ...lay at 20mA are adjustable although for flow application the display at 4mA is usually zero The position of the decimal point in the rate display is defined by the dP function To simplify calibration...

Page 9: ...onfiguration Access code CodE 0000 Function FunC 5td Linear Rate display at 4mA Zero 0 00 Rate display at 20mA 5PAn 100 00 Resolution rE5n 1 digit P button in display mode C P Local reset of total t r...

Page 10: ...s operated in the display mode Select PC of 4 20mA input 4 20 Current in mA Note PC is not available with lineariser See section 5 14 Display Summary of function 5CALE t Total scale factor Defines the...

Page 11: ...ntains two sub functions Select ConF Returns instrument to default configuration shown in section 5 2 LtAb Returns lineariser to defaults shown in section 6 5 Both instructions must be confirmed by en...

Page 12: ...12...

Page 13: ...arity with bi directional flow Use of the lineariser is described in section 6 of this instruction manual 5 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 14: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 15: ...s been activated see section 5 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 16: ...he or button When the required total scale factor has been set press E to enter the number and return to the 5CALE t prompt in the configuration menu 5 16 Clip off CLiP oFF To prevent totalisation of...

Page 17: ...g the P button will transfer control to the next digit When all the digits have been adjusted press E to return to the CodE prompt in the configuration menu The revised security code will be activated...

Page 18: ...Lineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is require...

Page 19: ...19...

Page 20: ...llowing break point 6 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 21: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 22: ...er the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or butt...

Page 23: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 24: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 25: ...tly the following table may help to identify the cause of the failure Symptom Cause Check No display and no voltage between terminals 1 3 or 12 3 if optional backlight is loop powered No power supply...

Page 26: ...New Rate Totalisers are supplied with the tag or application information specified when ordered thermally printed onto the rear panel adjacent to the terminals This tag information is not visible fro...

Page 27: ...sed and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 12 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switch any...

Page 28: ...28...

Page 29: ...ivated when the selected display rate or total equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally cl...

Page 30: ...y pressing the or button followed by the E button to return to the alarm menu 9 3 7 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 31: ...ate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs are...

Page 32: ...to the display mode Fig 15 Setpoint adjustment from the display mode To adjust an alarm setpoint select 5Px1 or 5Px2 and press P which will reveal the current setting Each digit of the setpoint may b...

Page 33: ...backlight 9 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the Rate Totaliser s 4 20mA input as shown in Fig 17 which increases the maximum Rate Totalis...

Reviews: