background image

9

.3.3  Alarm enable:  ‘EnbL’

This function allows each alarm to be enabled or
disabled  without  altering  any  of  the  alarm
parameters. To enable or disable the alarm select
'EnbL' from the alarm menu and press 

P

 which will

reveal  the  current  setting  ‘on’  or  ‘oFF’.    The
function can be changed by pressing the 

 or 

button  followed  by  the  

E

  button  to  return  to  the

alarm menu.

9.3.4  Type of alarm:  tYPE

This  function  conditions  the  alarm  to  operate  on
the rate or total display.   Alarm 1 and Alarm 2 may
both  be  rate  or  total  alarms,  or  one  may  be
conditioned for rate and the other for total. 
To check or change the type of alarm, select 'tYPE'
from the alarm menu and press 

P

 which will reveal

the current setting.  The function can be changed
by pressing the 

 or 

 button followed by the  

E

button to return to the alarm menu.   

Note:

   When  the  ‘tYPE’  function  is  changed  all

associated  alarm  functions  are  reset  to  default
conditions. 

9.3.5 Setpoint adjustment:   ‘5Px1’ and ‘5Px2’

The  setpoint  of  each  alarm  may  be  positioned
anywhere in the numerical display of the selected
rate or total display. 

The setpoint identification changes depending on
the  type  of  alarm.    If  the  alarm  has  been
conditioned  by the  ‘tYPE’  function  to  operate  on
the rate display the  setpoint will  be identified as
‘5Pr1’,  if  operating  on  the  total  display  it  will  be
identified 5Pt1.  
  
To adjust the setpoint select 'SPx1' or '5Px2' from
the alarm configuration menu and press  

P

 

which

will reveal the existing alarm setpoint.  The flashing
digit of the setpoint can be adjusted using the 

and  

 push buttons, and  the  

P

 button to  move

control  to  the  next  digit.    When  the  required
setpoint has been entered press 

E

 

to return to the

alarm configuration menu.

The alarm setpoints may also be adjusted when
the  Rate  Totaliser  is  in  the  display  mode,  see
section 9.3.12.

9.3.6  Alarm function:   ‘Hi.Lo’

Each alarm can be independently conditioned as a
high alarm or as a low alarm.   To check or change
the  alarm  function  select  'Hi.Lo'  from  the  alarm
menu  and  press  

P

  to  reveal  the  current  setting.

The function can be changed by pressing the 

 or

 button followed by the 

E

 button to return to the

alarm menu.

9.3.7  Alarm output status:   ‘no.nC’

Configures the solid state alarm output to be open
‘no’ or to be closed ‘nC’ in the non-alarm condition.
When deciding which is required, care should be
taken to ensure that the alarm output is fail safe as
illustrated in Fig 11.

‘no’ Alarm output open in non-alarm condition

‘nC’ Alarm output closed in non-alarm condition

CAUTION

When  the  4/20mA  supply  is  removed
from  the  loop  powered  Rate  Totaliser,
both alarm outputs will open irrespective
of configuration.  Therefore for fail safe
operation both alarm outputs should be
configured  to  be  open  in  the  alarm
condition ‘nC’.

To check or change the alarm output status, select
'no.nC'  from  the  alarm  configuration  menu  and
press 

P

 to reveal the setting.  The function may be

changed by pressing the 

 or 

 button followed

by the 

E

 

button to return to the alarm configuration

menu.

9.3.8  Hysteresis:   H5tr
Only functions on rate display

Hysteresis  is  shown  in  the  units  that  the  rate
display has been calibrated to display.
To  adjust  the  hysteresis  select  'H5tr'  from  the
alarm  menu  and  press  

P

  which  will  reveal  the

existing figure.  The flashing digit can be adjusted
using   the  

 and  

 push  buttons,  and  the  

P

button will move control to the next digit.  When the
required  hystersis  has  been  entered  press  

E

 

to

return to the alarm configuration menu.

e.g.  A BA558E calibrated to display a rate of 0 to
10000,  with  a  high  alarm  set  at  9000  and
hysteresis of 200 will perform as follows:

The high alarm will be activated when increasing
rate display equals 9000, but will not reset until the
rate display falls below 8800.

9.3.9  Alarm delay:   dELA

This function delays activation of the alarm output
for an adjustable time following the alarm condition
occurring.    The  delay  can  be  set  in  1  second
increments  between  0  and  3600  seconds.    If  a
delay is not required zero should be entered.  To
adjust  the  delay  select  'dELA'  from  the  alarm
configuration menu and press  

P

 which will reveal

the existing delay.  The flashing digit of the delay
can be adjusted using the 

 and 

 push buttons,

and the 

P

 button to move control to the other digits.

When the required delay has been entered press

E

 

to return to the alarm menu.

30

Summary of Contents for BA558E

Page 1: ...Issue 3 4th July 2014 BA558E General Purpose 4 20mA loop powered panel mounting Rate Totaliser Issue 3...

Page 2: ...ion using external current source 6 1 1 Example Adding break points to a new Rate Totaliser 6 2 Calibration using internal reference 6 2 1 Example Adding break points to a new Rate Totaliser 6 3 Error...

Page 3: ...vated Loading message displayed Configuration message displayed Model and firmware version displayed The BA558E Rate Totaliser starts functioning using configuration information stored in the instrume...

Page 4: ...mode Operating the or button will toggle the display to CLr YE5 with YE5 flashing operating the E button will then clear the grand total and Gt CLrd will be displayed to confirm the operation The ins...

Page 5: ...nce of less than 1k as shown in Fig 2 Note The negative reset terminal RS2 is internally connected to the negative 4 20mA input terminal 3 The total display may also be reset to zero by operating the...

Page 6: ...3 Installation Procedure a Cut the specified aperture in the panel To achieve an IP66 seal between the instrument enclosure and the instrument panel the aperture must have the tighter tolerances spec...

Page 7: ...as an accessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it...

Page 8: ...lay at 20mA are adjustable although for flow application the display at 4mA is usually zero The position of the decimal point in the rate display is defined by the dP function To simplify calibration...

Page 9: ...onfiguration Access code CodE 0000 Function FunC 5td Linear Rate display at 4mA Zero 0 00 Rate display at 20mA 5PAn 100 00 Resolution rE5n 1 digit P button in display mode C P Local reset of total t r...

Page 10: ...s operated in the display mode Select PC of 4 20mA input 4 20 Current in mA Note PC is not available with lineariser See section 5 14 Display Summary of function 5CALE t Total scale factor Defines the...

Page 11: ...ntains two sub functions Select ConF Returns instrument to default configuration shown in section 5 2 LtAb Returns lineariser to defaults shown in section 6 5 Both instructions must be confirmed by en...

Page 12: ...12...

Page 13: ...arity with bi directional flow Use of the lineariser is described in section 6 of this instruction manual 5 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 14: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 15: ...s been activated see section 5 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 16: ...he or button When the required total scale factor has been set press E to enter the number and return to the 5CALE t prompt in the configuration menu 5 16 Clip off CLiP oFF To prevent totalisation of...

Page 17: ...g the P button will transfer control to the next digit When all the digits have been adjusted press E to return to the CodE prompt in the configuration menu The revised security code will be activated...

Page 18: ...Lineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is require...

Page 19: ...19...

Page 20: ...llowing break point 6 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 21: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 22: ...er the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or butt...

Page 23: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 24: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 25: ...tly the following table may help to identify the cause of the failure Symptom Cause Check No display and no voltage between terminals 1 3 or 12 3 if optional backlight is loop powered No power supply...

Page 26: ...New Rate Totalisers are supplied with the tag or application information specified when ordered thermally printed onto the rear panel adjacent to the terminals This tag information is not visible fro...

Page 27: ...sed and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 12 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switch any...

Page 28: ...28...

Page 29: ...ivated when the selected display rate or total equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally cl...

Page 30: ...y pressing the or button followed by the E button to return to the alarm menu 9 3 7 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 31: ...ate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs are...

Page 32: ...to the display mode Fig 15 Setpoint adjustment from the display mode To adjust an alarm setpoint select 5Px1 or 5Px2 and press P which will reveal the current setting Each digit of the setpoint may b...

Page 33: ...backlight 9 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the Rate Totaliser s 4 20mA input as shown in Fig 17 which increases the maximum Rate Totalis...

Reviews: