background image

5

3.3  Pulse input

As shown in Fig 2, the BA534D will count pulses
from a wide variety of transducers  enabling it to
display the output from almost any flowmeter.

The instrument has one pulse input, but two sets
of input terminals enable it to accommodate
different types of transducers.   Terminals 5 and 6
are for pulse sources that need powering and
terminals 3 and 4 are for voltage pulse inputs.

Note:

 Only one pair of input terminals may be

used at a time.  i.e pulses can not be counted
from terminals 3 & 4 and from terminals 5 & 6 at
the same time.

The following table shows the switching
thresholds for the various transducers, plus the
maximum operating frequency and the input
terminal numbers.   For reliable counting the input
signal must fall below the lower threshold and rise
above the upper threshold.

Switching

thresholds

Freq

max

Input

terminals

Switch

100

1000

100Hz

5 & 6

Proximity

detector

1.2mA

2.1mA

5 kHz

5 & 6

Open

collector

2k

10k

5kHz

5 & 6

Magnetic

pick-off

0mV

20mV

peak

5kHz

3 & 4

Voltage

pulse

1.0V

3.0V

5kHz

3 & 4

3.4  Remote reset

The BA534D total display is reset to zero when
terminals 7 & 8 are connected together for more
than one second. Permanent interconnection of
these terminals will stop totalisation and may be
used as an inhibit function.  There is no practical
limit on the distance that the reset switch may be
from the totaliser.

Alternatively, the BA534D may be programmed so
that the total display is reset to zero when the 

Up

and 

Down

 push-buttons are operated

simultaneously for more than two seconds. – see
5.12

4.  INSTALLATION

4.1 Location

The BA534D rate totaliser is housed in a robust
IP66 glass reinforced polyester (GRP) enclosure
incorporating an armoured glass window and
stainless steel fittings.  It is suitable for exterior
mounting in most industrial environments,
including off-shore and waste water treatment.
Please consult BEKA associates if high vibration
is anticipated.

The BA534D enclosure is surface mounting.
Accessory kits described in sections 8.7 & 8.8 of
this manual enable the instrument to be mounted
onto a vertical or horizontal pipe, or directly onto a
flowmeter conduit entry.

The field terminals and the two mounting holes
are located in a separate compartment with a
sealed cover allowing the instrument to be
installed without exposing the display assembly.

The BA534D earth terminal is connected to the
internal EMC filters. For maximum radio frequency
interference rejection this terminal should be
connected to a local earth, or to an earthed cable
screen.
The BA534D enclosure is supplied with a bonding
plate to ensure electrical continuity between the
three conduit / cable entries.

4.2 Installation Procedure

Fig 3 illustrates the instrument installation
procedure.

a.

Remove the instrument terminal cover by
unscrewing the two captive 'A' screws.

b.

Mount the instrument on a flat surface and
secure with two M6 screws through the 'B'
holes.  Alternatively use one of the mounting
kits described in section 8.7 and 8.8

c.

Remove the temporary dust seals from the
three cable entries and install the required
glands, conduit fittings or blanking plugs.

Note:

  The temporary dust seals fitted for

transit do not maintain the IP66 protection of
the BA534D enclosure.

d.

Connect the field wiring to the terminals as
shown in Fig 4.

e.  Replace the instrument terminal cover and

evenly tighten the two 'A' screws.

Summary of Contents for BA534D

Page 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Page 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Page 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Page 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Page 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Page 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Page 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Page 8: ...8...

Page 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Page 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Page 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Page 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Page 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Page 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Page 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Page 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Page 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Page 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Page 19: ...19 Fig 10 Alarm menu structure...

Page 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Page 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Page 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Page 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Page 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Page 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Reviews: