13

5.14  Resetting grand total:   ‘CLr. Gtot’

The grand total is a separate sixteen digit counter
which duplicates the total display but is not zeroed
when the total display is reset to zero.  The grand
total may be viewed in the display mode in two
eight digit sections as described in section 2.2 of
this manual.

The grand total counter can only be reset to zero
from the 'CLr. Gtot' function in the main
programme menu.   To zero the grand total
counter select 'CLr. Gtot' and press 

which will

cause the instrument to display 'Clr. no' with 'no'
flashing.    Continuously press the 

Up

 or 

Down

push-buttons until 'CLr. YES' is displayed and
then press 

P

 which will result in a 'CLr 0000'

prompt with one digit flashing.  Using the 

Up

, and

Down

 buttons and the

  P

 button to move to the

next digit, confirm the request by entering the
password 'SurE'.  Note 'S' is entered as '5'.
Pressing

  E

 will then reset the grand total counter

to zero and return the instrument to the 'CLr. Gtot'
prompt in the main menu.

WARNING

After resetting the grand total
counter to zero the old grand total
can not be recovered.

5.15  Security code:  ‘CodE’

The calibration and conditioning of the instrument
may be protected by a four digit security code
which must be entered before access to the
programme menu is granted.   New instruments
are programmed with the default security code
0000 which allows unrestricted access to all
programming functions without entering a security
code.

To enter a new security code select 'COdE' from
the menu and press

  P

 which will cause the

instrument to display the current security code.
Each digit of the code can be changed using the

Up

 and

 Down

 push-buttons, and the 

P

 button to

move to the next digit.  When the required code
has been entered press

  E

 to return to the main

menu. The revised security code will be activated
when the indicator is returned to the display mode.

If the security code is lost, access to the
programmable functions can be obtained by
moving the internal security link to the override
position.   The original security code can then be
viewed by selecting 'CodE' from the main menu
and pressing

 P

.

To gain access to the security code link, remove
the instrument control cover by undoing the two
‘C’ screws – see Fig 3.

If the instrument is fitted with external push-
buttons the connecting ribbon cable should be
unplugged from the outer row of the five pin
connector.  The security code override link is
located on the inner row of the five pin connector
as shown in Fig 7.

Fig 7  Location of security override link

6.  CALIBRATION EXAMPLE

In this example a BA534D rate totaliser is
connected to a turbine flowmeter having a K-factor
of 1050.0 pulses per litre.   The flowmeter has a
magnetic pick-off with an output greater than
20mV peak at 5 litres per minute and a usable
range of 5 to 60 litres per minute.

The BA534D is required to display rate of flow in
litres per hour with a resolution of one litre and
total flow in cubic metres with a resolution of 0.01
cubic metres.   Totalisation is to stop when the
flow rate falls below 300 litres per hour.  The
display is to be updated twice per second and
filtering is required.   In this application the
operator needs to reset the total display to zero by
simultaneously pushing the 

Up

 and 

Down

 push-

buttons.  To prevent tampering the instrument
programme menu is to be protected by security
code 1209

Summary of Contents for BA534D

Page 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Page 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Page 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Page 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Page 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Page 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Page 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Page 8: ...8...

Page 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Page 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Page 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Page 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Page 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Page 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Page 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Page 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Page 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Page 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Page 19: ...19 Fig 10 Alarm menu structure...

Page 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Page 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Page 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Page 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Page 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Page 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Reviews: