22

8.2.11  Access Setpoint:  ‘AcSP’

This function activates a separate menu that
provides direct access to the alarm setpoints
when the instrument is in the display mode.  See
section 8.2.12 for a full description.    An operator
may therefore adjust the alarm setpoints without
having access to the programme and alarm
menus.  Further protection is provided by a
separate security code.

This direct access menu may be enabled and a
separate security code entered from the 'AcSP'
function in the main programme menu as shown
in Fig 11.  To change the menu parameters select
'AcSP' from the programme menu and press 

P.

  

This will display the enable prompt 'EnbL'.

Press 

P

 again to reveal if the direct access menu

is 'On' or 'OFF'.  The 

Up

 or 

Down

 buttons will

toggle the display between the two conditions.

If 'OFF' is selected, the operator will not have
access to the setpoints from the display mode.
Return to the 'AcSP' prompt in the main menu by
pressing

 E

 twice.

If 'On' is selected, the operator will have direct
access to the alarm setpoints from the display
mode via a separate optional security code.   To
define this four digit numeric code press 

E

 to

return to the 'EnbL' prompt followed by the 

Up

 or

Down

 button to select the access code prompt

'AcCd'.   Pressing 

will then reveal the current

security code.  The flashing digit of the code may
be changed by operating the 

Up

 or 

Down

 push-

buttons and pressing the 

P

 button will transfer

control to the next digit.  When the required code
has been entered, press 

E

 twice to return to the

'AcSP' prompt in the programme menu.

Entering code 0000 will disable the security code
allowing direct access to the setpoints in the
display mode by pressing the

  P

 and 

Up

 buttons

simultaneously.

New instruments with alarms are supplied with the
security code set to 0000

8.2.12  Adjusting alarm setpoints from the
            display mode

Access to the two alarm setpoints from the
instrument display mode is obtained by operating
the 

P

 and 

Up

 push-buttons simultaneously as

shown in Fig 11.  If the setpoints are not protected
by a security code the alarm setpoint prompt
'SPr1' or 'SPt1' will be displayed depending upon
whether a rate or total alarm has been
programmed.

If the setpoints are protected by a security code,
'COde' will be displayed first.  Pressing 

P

 again

will enable the alarm security code to be entered
digit by digit using the 

Up

 and 

Down

 buttons to

change the flashing digit and the 

P

 push-button to

move control to the next digit.  If the correct code
is entered pressing 

E

 will then cause alarm

setpoint prompt 'SPx1' to be displayed. If an
incorrect security code is entered, or a button is
not pressed within ten seconds, the instrument will
automatically return to the display mode.

Once within the menu pressing the 

Up

 or 

Down

buttons will toggle the display between the two
alarm setpoint prompts 'SPx1' and 'SPx2'.

Fig 11 Setpoint adjustment from the display mode

To adjust an alarm setpoint select 'SPx1' or 'SPx2'
and press

  P

 which will reveal the current setting.

Each digit of the setpoint may be adjusted using
the

 Up

 and 

Down

 push-buttons, and the

 P

 button

to move control to the next digit.  When the
required setpoint has been entered, pressing 

E

will return the display to the 'SPx1' or 'SPx2'
prompt from which the other setpoint may be
selected, or the indicator may be returned to the
display mode by pressing 

E

 again.

Note:

 Direct access to the alarm setpoints is only

available when the menu is enabled - see section
8.2.11

Summary of Contents for BA534D

Page 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Page 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Page 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Page 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Page 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Page 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Page 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Page 8: ...8...

Page 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Page 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Page 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Page 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Page 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Page 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Page 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Page 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Page 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Page 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Page 19: ...19 Fig 10 Alarm menu structure...

Page 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Page 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Page 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Page 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Page 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Page 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Reviews: