All new BA534D rate totalisers are supplied
calibrated as requested at the time of ordering.  If
calibration information is not supplied, the
instrument will be conditioned for an open
collector input, with SCALE-r and SCALE-t set to
1 and a  timebase of seconds.

5.3  Summary of programmable functions

This section summarises all the programmable
functions.  When read in conjunction with Fig 6 it
provides a quick aid for programming the
instrument.  If more detail is required, each
section contains a reference to a full description of
the function.

SUMMARY

Display

Description of function

‘UpdAtE’

Display update time

Allows the interval between
display updates to be selected.
See section 5.4

'InPut'

Type of input

Enables one of five types of input
to be selected:
UOLtS

Voltage pulse

COIL

Magnetic pick-off

Pr.dEt

NAMUR proximity
detector.

COntACt

Switch contact

OP.COL

Open collector

See section 5.5

'd.P.'

Decimal points

Defines the position of the decimal
point in both the rate and total
displays and enables the rate and
total displays to be interchanged.
See section 5.6

‘dISPLAY.2’ Lower display

Turns the lower display, which
normally shows rate, on or off.
See section 5.7

Display

Description of function

'SCALE-r' Rate Scale Factor

Defines the arithmetic relationship
between the pulse input frequency
and the rate display.  May be
adjusted between 0.001 and
99999999.
When used with a flowmeter,
SCALE-r should be set to the
flowmeter K factor (pulses per unit of
measurement) if the rate display is
required in the same flow units as the
K factor.
See section 5.8

't-bASE'

Timebase

Selectable multiplier to display  flow
rate in units per second, per minute
or per hour.
Select:

tb-1

for flow / second

tb-60

for flow / minute

tb-3600 

for flow / hour

See section 5.9

'FILtEr'

Rate filter

Adjustable digital filter to reduce
noise on the rate display.  Two
parameters each adjustable between
0 and 9.
See section 5.10

'SCALE-t' Total Scale Factor

Defines the arithmetic relationship
between the number of input pulses
and the total display.

 

May be adjusted between 0.001 and
99999999.
When used with a flowmeter SCALE-
t should be set to the flowmeter K
factor (pulses per unit of
measurement).

 

See section 5.11

'CLIP-OFF'  Clip off

To prevent the totalisation of very low
flow rates, clip-off enables the user to
select a flow rate below which
totalisation is inhibited.
See section 5.12

Summary of Contents for BA534D

Page 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Page 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Page 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Page 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Page 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Page 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Page 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Page 8: ...8...

Page 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Page 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Page 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Page 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Page 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Page 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Page 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Page 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Page 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Page 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Page 19: ...19 Fig 10 Alarm menu structure...

Page 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Page 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Page 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Page 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Page 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Page 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Reviews: