background image

12

During commissioning it is recommend that
initially the second digit is set to 0 (off) and the
first digit is adjusted to provide acceptable rate
display stability. The second digit should then be
increased until the selected step size is greater
than the noise on the display signal, at which
setting the rate display will again become stable.
These will be the optimum filter parameters for
acceptable rate display stability and a fast
response to a large rate signal change.

To check or change the filter select 'FILtEr' from
the main menu and press 

P

 to reveal the current

settings.   Pressing the 

Up

 or 

Down

 button will

change the flashing digit and 

P

 will transfer control

to the second digit.  While making adjustments the
filtered rate display is shown on the lower display
so that stability can be assessed.  When set as
required, press the 

E

 button to enter the revised

parameters and return to the main menu.

5.11  Total scale factor:   ‘SCALE-t’

This factor defines the arithmetic relationship
between the number of input pulses and the total
display.  SCALE-t is a dividing factor that may be
adjusted between 0.001 and 99999999.   See Fig
5.

When used with a flowmeter  SCALE-t should be
set to the K-factor of the flowmeter  i.e. the
number of pulses the flowmeter produces for a
unit of flow.    If the BA534D total display is
required in units different from those in which the
flowmeter K factor is specified, a conversion factor
will be required.

e.g.  If the flowmeter has a K factor of 45.6 pulses
per litre and the BA534D total display is required
in units of 1,000 gallons, then  SCALE-t should be
set to the number of pulses produced by the
flowmeter per 1,000 gallons:

           

45.6 x 4.54609 x 1000

207,301.7 pulses per 1000 gallons

.
    (there are 4.54609 litres in a UK gallon)

To check or change the total scale factor select
'SCALE-t' from the main menu and press 

P

 to

reveal the existing setting, one digit will be
flashing.  The value of the flashing digit can be
changed by pressing the 

Up

 or 

Down

 buttons.

When this digit is correct pressing 

P

 will transfer

control to the next digit.

To position the decimal point in the scaling factor,
move the flashing digit to the left hand side of the
required decimal point position and
simultaneously press the 

Up

 and 

Down

 buttons.

When the required total scale factor has been
entered, press 

E t

o store the number and return to

the main menu.

5.12  Clip-off:  ‘CLIP-OFF’

To prevent totalisation of very low flow rates,
which over long periods may result in significant
totalisation errors, the BA534D may be
programmed to stop totalising when the flow rate
falls below an adjustable threshold.

To check or change the clip-off threshold select
'CLIP-OFF' from the main menu and press 

P

which will reveal the current setting.  The
threshold is shown in the units already selected
for the flow rate display.  One digit will be flashing.
The value of the flashing digit may be changed by
pressing the 

Up

 or 

Down

 buttons. When this digit

is correct pressing 

P

 will transfer control to the

next digit.    When clip-off is set as required, press
the

 E

 button to enter the revised figure and return

to the main programme menu.

If the flow rate falls below the entered threshold,
the rate display will show zero flow, totalisation will
stop and the HOLD annunciator will be activated.
The flow indicator will rotate for 2 seconds each
time an input pulse is received   i.e. at input
frequencies above  0.5Hz it will appear to rotate
continuously.

Note:  

When the rate scale factor SCALE-r, the

timebase t-bASE, or the position of the rate
display decimal point are changed, clip-off will
automatically be reset to zero.  If required, a new
clip-off threshold may then be entered.

5.13  Local reset of total display:
         ‘LOC. rSEt’

When activated this function enables the operator
to reset the BA534D total display to zero in the
display mode by operating the 

Up

 and

 Down

push-buttons simultaneously for more than two
seconds.   To check the status of the local reset
function select 'LOC.rSEt' from the menu and
press

 P

  which will reveal if the function is 'On' or

'OFF'.   If necessary press the 

Up

 or 

Down

 button

to change the setting, followed by the

 E

 button to

return to the main menu.

The total display may also be reset to zero
remotely by connecting terminals 7 and 8
together.  See section 3.4 of this manual.

Summary of Contents for BA534D

Page 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Page 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Page 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Page 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Page 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Page 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Page 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Page 8: ...8...

Page 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Page 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Page 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Page 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Page 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Page 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Page 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Page 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Page 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Page 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Page 19: ...19 Fig 10 Alarm menu structure...

Page 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Page 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Page 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Page 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Page 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Page 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Reviews: