background image

18

8.  ACCESSORIES

8.1  Units of measurement and instrument
       identification

All BA534D rate totalisers are fitted with a display
label behind the armoured glass window.  This
label can be supplied printed with any units of
measurement and tag information specified when
the instrument is ordered.  Alternatively the
information may be added on-site via an
embossed strip, dry transfer or a permanent
marker.

To gain access to the display label remove the
terminal cover by unscrewing the two 'A' screws
which will reveal two concealed 'D' screws.
Remove all four 'D' screws and carefully lift off the
front of the instrument - see Fig 3.    Add the
required legend to the display label, or replace
with a new pre-printed label which is available
from BEKA associates.

The BA534D can also be supplied with a blank or
custom engraved stainless steel plate secured by
two screws to the side of the instrument
enclosure. This plate can accommodate:

       1 row of 9 alphanumeric characters 10mm high

   or 1 row of 11 alphanumeric characters 7mm high

   or 2 rows of 18 alphanumeric characters 5mm
        high

8.2  Alarms

The BA534D can be supplied with two solid state
single pole outputs which may be independently
programmed as high or low, rate or total alarms
with normally open or normally closed outputs.

WARNING

These alarm outputs should not be used
for critical safety applications such as a
shut down system.

When the BA534D power supply is turned off or
disconnected, both BA534D alarm outputs will
open irrespective of whether normally open or
normally closed outputs have been selected.
When designing a system an open output should
therefore be the alarm condition.

Alarm annunciators on the instrument display
indicate the status of both alarms. If an alarm
delay or silence time has been selected the
annunciator will flash during the delay or silence
period.

Programmable functions for each alarm include
adjustable setpoint, alarm delay time and alarm
accept time.   Hysteresis may be applied to rate
alarms.

The BA534D total display is up-dated and
compared with the programmed alarm setpoint
twice per second, irrespective of the display
update time selected.  This may result in the total
alarm being delayed for up to half a second after
the total has exceeded the setpoint.

8.2.1  Solid state output

Each alarm has a galvanically isolated single pole
solid state switch output as shown in Fig 8.  The
outputs are polarised and current  will only flow in
one direction.   Terminals A1 and A3 should be
connected to the positive side of the supply.

Ron

=

5

 + 0.6V

Roff

=

greater than 180k

Note:

  Because of the series protection diode

some test meters may not detect a closed
alarm output

Fig 8 Equivalent circuit of each alarm output

Fig 9  Typical alarm application

Summary of Contents for BA534D

Page 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Page 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Page 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Page 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Page 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Page 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Page 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Page 8: ...8...

Page 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Page 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Page 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Page 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Page 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Page 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Page 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Page 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Page 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Page 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Page 19: ...19 Fig 10 Alarm menu structure...

Page 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Page 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Page 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Page 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Page 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Page 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Reviews: