background image

Fig 13 Equivalent circuit of each alarm output

9.3.2   Ex nA certification

Each alarm output is a separate galvanically isolated
Ex nA circuit with the following input parameters:

Ui

=

30V dc

Ii

=

200mA

This allows each alarm output to switch any dc circuit
providing  that  in  normal  operation  the  maximum
supply  voltage  is  not  greater  than  30V  dc  and  the
switched current is not greater than 200mA.  

Providing that the BA314NG Tachometer is correctly
installed in Zone 2 the two alarm outputs may be used
to switch suitably protected equipment located in Zone
1 or 2 of a hazardous area, or equipment located in a
safe area.    

Fig  14  shows  a  typical  application  in  which  a
BA314NG  Tachometer  is  mounted  in  Zone 2  is
displaying the output from a Flameproof Ex d 2-wire
proximitor located in Zone 1.    Alarm 1 is switching an
Ex e sounder in Zone 1 and alarm 2 is switching a
sounder located in the safe area.

Fig 14  Typical alarm application

(Shown without recommended screened cables)

To  comply  with  the  requirements  of  EN 60079-14

Electrical installations design, selection and erection

,

each  of  the  wires  entering  the  hazardous  area
should be individually fused and contain a means of
isolation.    These  two  requirements  are  frequently
satisfied by using fuse holders with easily removable
fuses and removing the fuses to achieve isolation.
This is a satisfactory method at the low voltages and
currents common in instrumentation systems. Clear
identification of, and easy access to the means of
isolation is essential for their effective use. It is also
necessary to ensure that the maintenance procedure
makes  sure  that  unauthorised  re-closure  of  the
switches  does  not  occur.  It  is  not  considered
necessary to have a means of isolation or electrical
protection  for  the  screen.      Fig  2  illustrates  an
example of this type of fused terminal block.

For  some  application  Ex nA  instrumentation
energised  by  a  current  limited  power  supply  or
instrument  that  can  be  switched  off,  is  often
considered  adequate  and  to  comply  with  the
requirements of the standard.

9.3.3  Configuration and adjustment

When  a  BA314NG  is  supplied  with  alarms  the
configuration menu is extended as shown in  Fig 15
which for simplicity only shows alarm AL1 configured
to operate as a speed alarm.  The run-time options
are identical except that a run-time alarm can not
have hysteresis.   Alarm AL2 functions are identical
to alarm AL1.

The following table summarises each of the alarm
configuration  functions  and  includes  a  cross
references to more detailed information.   Again only
the functions on alarm AL1 are listed.

    Display       Summary of function

EnbL

Alarm enable

Enables  or  disables  the  alarm  without
changing the alarm parameters.
See section  9.3.4

tYPE

Type of alarm

Defines whether  the alarm  operates on
the speed or run-time display. 
See section 9.3.5

5P1.5peed

Alarm setpoint 1

   or

Adjusts the alarm setpoint.  The

5P1.Hour5s

alarm is activated when the speed or

run-time display equals the setpoint.

Note:

 

5P15

  is  displayed  for  a  speed

alarm and 

5P1H

 for a run-time alarm.

See section 9.3.6

HI

 

.

 

LO

Alarm function

Defines whether the alarm has a high or
low function.
See section 9.3.7

31

Summary of Contents for BA314NG

Page 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Page 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Page 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Page 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Page 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Page 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Page 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Page 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Page 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Page 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Page 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Page 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Page 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Page 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 16: ...16...

Page 17: ...17...

Page 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Page 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Page 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Page 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Page 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Page 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Page 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Page 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Page 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Page 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Page 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Page 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Page 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Page 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Page 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Page 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Page 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Page 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Page 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Page 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Reviews: