1.  DESCRIPTION

The BA314NG is an Ex nA and Ex tc certified, field
mounting  Tachometer  primarily  intended  for
measuring  rotational  speed  within  a  Zone  2  or  22
hazardous area.  To assist with routine maintenance,
the Tachometer  includes a run-time clock that records
the number of hours that the monitored machinery has
been  operating.    The  BA314NG  is  controlled  and
configured  via  the  four  front  panel  push  buttons,  a
user defined four digit code may be entered to prevent
accidental  access  to  the  instrument's  configuration
menu.

This instruction manual supplements the abbreviated
instruction sheet supplied with each instrument.

The  BA314NG  has  been  issued  with  a  Type
Examination  Certificate  ITS16ATEX48409X  by
Notified  Body  Intertek  Testing  and  Certification  Ltd.
This confirms compliance with the type of protection
requirements for non-sparking Ex nA apparatus, and
for dust ignition protection by enclosure Ex tc.   This
certificate has been used to confirm compliance with
the European ATEX Directive 2014/34/EU.  

For international applications the BA314NG also has
IECEx certification which is described in Appendix 2.

For  applications  in  the  USA  and  Canada  the
BA314NG  has  ETL  and  cETL  approval,  see
Appendix 3.

2.  OPERATION

Fig  1  shows  a  simplified  block  diagram  of  the
BA314NG Tachometer.  The instrument can accept
pulses from most types of sensor and display speed
per  second,  minute  or  per  hour,  plus  run-time  in
hours on a separate display.   

The BA314NG has a single pair of input terminals for
connection to all types of sensor. When connected to
a  sensor  requiring  energising,  such  as  a  switch
contact,  open  collector  or  a  two  wire  proximity
detector, an external link between terminals 3 and 4
connects power to the sensor input terminals.   An
isolated  pulse  output  can  be  configured  to
synchronously  retransmit  the  pulse  input,  or  a
frequency  divided  frequency  output  with  a  defined
pulse width.  

Factory  fitted  accessories  include  an  internally
powered  display  backlight,  dual  alarms  and  an
isolated 4/20mA output which may be configured to
retransmit any part of the speed display.  

Fig 1  BA314NG block diagram

4

Summary of Contents for BA314NG

Page 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Page 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Page 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Page 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Page 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Page 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Page 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Page 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Page 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Page 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Page 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Page 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Page 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Page 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 16: ...16...

Page 17: ...17...

Page 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Page 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Page 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Page 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Page 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Page 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Page 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Page 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Page 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Page 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Page 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Page 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Page 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Page 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Page 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Page 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Page 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Page 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Page 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Page 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Reviews: