background image

7.  CONFIGURATION EXAMPLE

In this example a BA314NG Tachometer is connected
to  a  proximity  detector  producing  105  pulses  per
revolution.

The BA314NG is required to display rotational speed
in RPM with a resolution of one RPM.   The run-time
clock  is  to  operate  when  the  shaft  speed  exceeds
5   RPM.   The   display   is   to   be   updated   twice   per
second.

For this application the  operator needs to reset the
run-time display to zero from the display mode, but
should not be able to reset the grand total run-time
from  the  display  mode.    To  prevent  tampering  the
instrument configuration menu is to be protected by
security code of 1209.

7.1  Configuration procedure

The BA314NG Tachometer may be configured on-site
without disconnection from the power supply or from
the proximity detector.

Step 1

Enter the configuration menu

Enter  the  configuration  menu  by
simultaneously  pressing  

(

 and  

)

.

Assuming a security code has not already
been entered the instrument will respond
by  displaying  

inPut

  which  is  the  first

function  in  the  configuration  menu.    See
Fig 10.

Step 2

Select the type of input & debounce

With  

inPut

 displayed press  

(  

which will

reveal the sub-menu.   Using the 

&

 or 

*

button  select  

inP

 

.

 

tYPE

  and  press  

(  

to

reveal the current input.   The Tachometer
is  required  to  work  with  a  proximity
detector  so  again  using  the  

&

 or  

*

button  select  

Pr.

 

dEt

 followed  by  

)  

to

return to the  

inP

 

.

 

tYPE

 prompt in the sub-

menu.
Using  the  

&

 or  

*

 button  select

dEbouncE

  from  the  sub-menu  and  press

(

.  Using  the  

&

 or  

*

 button  select

dEFAuLt

 which will provide moderate pulse

edge noise protection.  If the Tachometer
is  subsequently  found  to  miscount  the
noise   rejection   can   be   increased.     Enter
the   selection   and   return   to   the  

inPut

prompt  in  the  configuration  menu  by
pressing the 

button twice.

See 6.4, 6.5 and 6.6

Step 3

Select  the  interval  between  display
updates

Using the  

&

 or  

*

 button select  

uPdAtE

in the configuration menu and press 

to

reveal  how  frequently  the  Tachometer
display is updated.

Using the  

&

 or  

*

 push button select

0

 

.

 

5

  (0.5  seconds  i.e. 2 display  updates

per  second).    Enter  the  selection  and
return  to  the  

uPdAtE

  prompt  in  the

configuration  menu  by pressing  the  

)

button.
See 6.7

Step 4

Run-time display 

Using the 

&

 or 

*

 button select 

di5P-2

in the configuration menu and press  

(

to select if the run-time display is  

on

 or

oFF

.    The  Tachometer  is  required  to

display run-time therefore using the  

&

or  

*

 button select  

on

 and press  

)  

to

enter  the  selection  and  return  to  the

di5P-2

 prompt in the configuration menu.

See 6.8

Step 5

Position  of  decimal  point  in  speed
display.

Select  

dP

  from  the  configuration  menu

and press 

(

. The speed display will be

activated  and  identified  by  the  Rate
annunciator.  Using the  

&

 or  

*

 push

button  position the  decimal point to  the
right of the least significant digit to give a
total display resolution of 1.
Finally press the  

)  

button to enter the

selection and return to the  

dP

 prompt in

the configuration menu.

See 6.9

Step 6

Enter the speed scale factor

5CALE.5

  is  a  dividing  factor  adjustable

between 0.0001 and 99999 that enables
the Tachometer to  display speed  in  the
required  engineering  units.    The  speed
display  timebase  is  determined  by

t-bA5E

 that is adjusted in Step 7.

In  this  example  the  Tachometer  speed
display  is  required  in  revolutions  per
minute.  The proximity detector produces
105  pulses  per  revolution  therefore

5CALE

 

.

 

5

 should therefore be adjusted to

105.0.

Using the  

&

 or  

*

 push button select

5CALE.5

  from  the  configuration  menu

and press 

to reveal the existing value

with one digit flashing.  This should be
changed  to  105.0  using  the  

&

 or  

*

push  button  to  adjust  the  flashing  digit
and the  

(  

button to transfer control to

the next digit and to position the decimal
point.  Finally, enter the new value and
return  to  the  

5CALE

 

.

 

5

  prompt  in  the

configuration menu by pressing 

)

.

See 6.10

25

Summary of Contents for BA314NG

Page 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Page 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Page 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Page 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Page 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Page 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Page 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Page 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Page 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Page 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Page 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Page 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Page 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Page 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 16: ...16...

Page 17: ...17...

Page 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Page 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Page 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Page 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Page 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Page 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Page 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Page 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Page 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Page 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Page 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Page 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Page 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Page 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Page 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Page 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Page 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Page 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Page 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Page 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Reviews: