background image

9.3.11  Alarm silence time:  

5IL

The  alarm  silence  function  is  primarily  intended  for
use  in  small  installations  where  the  alarm  output
directly operates an annunciator such as a sounder.
When the alarm silence time is set to any figure other
than  zero,  the  

(  

push  button  becomes  an  alarm

accept button.

After an alarm has occurred, operating the 

(

 button

will cause the alarm output to revert to the non-alarm
condition for the configured alarm silence time.  When
an alarm is silenced the alarm annunciator will flash
until the silence time expires.

To adjust the alarm silence time select 

5iL

 using the

&

 or 

*

 push button in the selected alarm sub-menu

and  press  

(  

which  will  reveal  the  existing  alarm

silence time in seconds with one digit flashing.  The
required  delay  time  can  be  entered  using  the

&

 or 

*

 push button to adjust the flashing digit and

the  

(

  button  to  transfer  control  to  the  next  digit.

When set as required press 

to enter the value and

return to the 

5iL

 prompt in the alarm sub-menu.

9.3.12  Flash display when alarm occurs:  

FL5H

In  addition  to  the  two  alarm  annunciators  at  the
bottom left hand side of the Tachometer display which
show the status of both alarms, this function provides
an even  more  conspicuous indication that an alarm
condition has occurred.

When enabled, this function alternates the speed or
run-time display between the numerical value and the
alarm identification AL1 or AL2 when an alarm occurs.

Using the 

&

 or 

*

 push button select 

FL5H

 from the

selected alarm sub-menu and press  

(  

to check or

change the function.  The  

&

 or 

*

 push button will

toggle the function between 

oFF

 and 

on

, when set as

required, press the  

)  

button to return to the  

FL5H

prompt in the alarm sub-menu.

9.3.13  Access Setpoint:  

AC5P

This function activates a separate menu that provides
direct  access  to  the  alarm  setpoints  when  the
Tachometer is in the display mode by simultaneously
operating  the  

(

 and 

*

  buttons.   An  operator  can

therefore  adjust  the  alarm  setpoints  without  having
access  to  the  configuration  and  alarm  sub-menus.
Protection  against  unauthorised  or  accidental
adjustment is provided by a separate security access
code.

Using the 

&

 or 

*

 push button select 

AC5P

 from the

configuration  menu  and  press  

(  

to  reach  the

enable  function  

EnbL

.  Pressing  

(  

will  reveal  the

existing  setting  which  can  be  toggled  between  

on

and  

oFF

 by  pressing  the  

&

 or 

*

 push  button.

When set as required, press the 

button to return

to the  

EnbL

 prompt from which a separate security

access code can be entered using the 

ACCd

 function

which  can  be  selected  using  the  

& or *

 push

button.

To enter a new security code select  

ACCd

 from the

sub-menu  and  press  

(

  which   will   cause   the

Tachometer to display  

0000

 with one digit flashing.

The  flashing  digit  may  be  adjusted  using  the

&

 and 

*

  push  button,  when  set  as  required

operating the  

(  

button will transfer control to the

next digit.   When all the digits have been adjusted
press 

to return to the 

ACCd

 prompt.  The revised

security code will be activated when the Tachometer
is returned to the display mode.   Default security
access  code  0000  will  disable  the  security  code
allowing direct access to the setpoints in the display
mode  by  pressing  the  

(

 and 

*  

buttons

simultaneously.

Please contact BEKA associates sales department if
the security code is lost.

9.3.14  Adjusting alarm setpoints from the
            display mode

Access  to  the  two  alarm  setpoints  from  the
Tachometer display mode is obtained by operating
the  

(

 and 

*  

push  buttons  simultaneously  as

shown in Fig 16.  If the setpoints are not protected
by  a  security  code  the  alarm  setpoint  prompt

5P1.5peed

 or  

5P1.Hour5

 will be displayed depending

upon whether a speed or run-time alarm has been
configured.    If  the  setpoints  are  protected  by  a
security code, 

CodE

 will be displayed first.  Pressing

(  

again  will  allow  the  alarm  setpoint  security

access code to be entered digit by digit using the

&

 or 

*

 buttons to adjust the flashing digit and the

push button to move control to the next digit.  If

the  correct  code  is  entered  pressing

  )  

will  then

cause alarm setpoint prompt 

5P1.5peed

 or 

5P1.Hour5

to  be  displayed.  If  an  incorrect  security  code  is
entered,  or  a  button  is  not  pressed  within  ten
seconds, the instrument will automatically return to
the display mode.   Once within the menu pressing
the 

&

 or 

*

 buttons will toggle the display between

the two alarm setpoint prompts 

5P1

x and 

5P2

x.

35

Summary of Contents for BA314NG

Page 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Page 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Page 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Page 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Page 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Page 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Page 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Page 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Page 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Page 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Page 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Page 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Page 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Page 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 16: ...16...

Page 17: ...17...

Page 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Page 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Page 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Page 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Page 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Page 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Page 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Page 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Page 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Page 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Page 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Page 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Page 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Page 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Page 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Page 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Page 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Page 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Page 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Page 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Reviews: