background image

Step 7

Enter the speed timebase

The  speed  timebase  determines  if  the
Tachometer  displays  speed  per  second,
per minute or per hour.   In this example
revolutions per minute are required.
Using  the  

&

 or  

*

  push  button  select

t-bA5E

  from  the  configuration  menu  and

press 

(

.  Again using the 

&

 or 

*

 push

button select 

tb-60

 from the three options

which will multiply the speed display by 60.
Enter  the  selection  and  return  to  the

t-bA5E

 prompt in the configuration menu

by pressing 

)

.

See 6.11

Step 8

Adjust the display filter

The  digital  display  filter  has  two
independent  adjustable  parameters
enabling  the   rate   display   response   to  be
tailored  for  optimum  performance.    The
filter  parameters  are  controlled  by  a  two
digit  number.    The  first  digit  defines  the
amount of filtering applied to the  display,
for initial configuration it is recommended it
is set to 2 which is a time constant of 4.3
seconds.
The second digit defines the deviation from
the displayed speed at which the filtering,
defined by the first digit, will be overridden
and  the  Tachometer  speed  display  will
move  rapidly  to  the  new  value.    It  is
recommended  that  the  second  digit  is
initially set to 0.

After  configuration  both  parameters  may
require  further  adjustment  to  provide  a
stable  display  with  an  acceptable  step
response.

To allow the effect of filter changes to be
seen immediately, the live speed display is
shown on the lower display in place of run-
time while the filter parameters are shown
and being adjusted on the upper display.

Using  the  

&

 or  

*

  push  button  select

FiLtEr

  from  the  configuration  menu  and

press 

(

.   The  first  digit,  which  controls

the filter time constant, will be flashing and
should be set to 

2

 using the 

&

 or 

*

 push

buttons.  The 

button will transfer control

to the second digit, which controls the step
response  and  should  be  set  to  

0

 in  the

same way.  Finally, enter the selection and
return  to  the  

FiLtEr

 prompt  in  the

configuration menu by pressing 

)

.

See 6.12

Step 9

Define clip-off

In  this  example  the  run-time  clock  is
required  to  operate  when  the  display
speed equals or exceeds 5 RPM.   The
clip-off threshold should therefore be set
to 5.

Using the  

&

 or  

*

 push button select

Clp  oFF

 from  the  configuration  menu.

Press  

(  

which  will  reveal  the  current

clip-off  threshold  in  RPM  i.e.  the  same
units  already  selected  for  the  speed
display. Adjust the display to 

00005

 using

the 

&

 or 

*

 push buttons to adjust the

flashing  digit  and  the  

(  

button  to

transfer control to the next digit.  Finally,
enter   the   new   clip-off   threshold   and
return  to  the  

CLp-oFF

 prompt  in  the

configuration menu by pressing 

)

.

See 6.13

Step 13 Local reset of total and grand total

Two  separate  functions  in  the  

LoC  clr

sub-menu  may  be  individually  activated
to allow the operator to reset the run-time
display and grand total run-time from the
display  mode  without  entering  the
configuration menu.

In this example the operator is required
to  reset the run-time display but not the
grand total run-time when the BA314NG
Tachometer is in the display mode.
Using the 

&

 or 

*

 button select 

LoC clr

in the configuration menu and press  

(

which will reveal the sub-menu.   Again
using the 

&

 or 

*

 button select the local

total reset function 

clr tot

 and press 

(

.

This is required therefore using the 

&

 or

*

 button  select  

on

 followed  by  

)  

to

return to the  

clr tot

 prompt in the sub-

menu.

Using  the  

&

 or  

*

 button  select  the

local grand total  run-time reset function

clr  gtot

 and  press  

(

.    This  is  not

required  therefore  using  the  

&

 or  

*

button  select  

oFF

.    Enter  the  selection

and return  to  the   

Loc clr

  prompt  in

the configuration menu  by pressing the

)

 button twice.

See 6.15 and 6.16

26

Summary of Contents for BA314NG

Page 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Page 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Page 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Page 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Page 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Page 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Page 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Page 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Page 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Page 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Page 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Page 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Page 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Page 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 16: ...16...

Page 17: ...17...

Page 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Page 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Page 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Page 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Page 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Page 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Page 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Page 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Page 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Page 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Page 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Page 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Page 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Page 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Page 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Page 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Page 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Page 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Page 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Page 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Reviews: