Bus Trace function
FC5101 and FC5102
77
Version: 2.0
The following window opens:
Fig. 57: CAN Monitor - options
Device-ID:
The ID that the System Manager has assigned to the FC510x monitor channel must be entered
here:
Fig. 58: Entering the device ID
Storing:
The size of the ring buffer memory for the screen display (
Display
) and for that file output (
File
) can
be set here.
Display:
A filter for the display output can be specified here.
Trigger
: Trigger conditions that will stop the measurement can be specified here. It is possible, for instance,
for a specific otherwise unused output to be set when an error occurs, and to trigger off this bit in the output
module's RxPDO.
Post Trigger:
This can be used to specify how many telegrams are still to be recorded after the trigger
condition has occurred. The number of telegrams recorded prior to occurrence of the trigger condition is only
restricted by the specified buffer size.