Mounting and cabling
EP7402-0057
21
Version: 1.3
3.2.2.3
Supply voltage output X60
The supply voltage output is intended for EtherCAT devices that are connected to
.
CAUTION
The outgoing peripheral voltage Up‘ is not switched off when the incoming peripheral volt-
age U
P
is switched off. (from hardware version 03)
Actuators at the supply voltage output remain active.
• To safely switch off actuators at the supply voltage output, use
NOTE
The outgoing supply voltages are not electrically isolated.
(from hardware version 03)
The analog specifications of EtherCAT Box modules with analog inputs or outputs may not be met under
certain circumstances.
3
1
2
4
Fig. 3: M8 socket
Contact
Symbol
Description
Wire color
1
24V Us'
Control voltage
Brown
2
24V Up'
Peripheral voltage
1)
White
3
GND
Common ground potential for both
output voltages
2)
Blue
4
GND
Black
1)
Up‘ is branched off from different supply voltages, depending on the hardware version:
• From hardware version 03:
Up‘ is branched off from the incoming control voltage U
S
• Up to and including hardware version 02:
Up‘ is branched off from the incoming peripheral voltage U
P
at
.
2)
Up to and including hardware version 02: GND
S
is connected to pin 3, GND
P
to pin 4. Starting with
hardware version 03, both pins are connected to the same ground potential GND
S
.
Suitable connection cables can be found in the chapter