Commissioning
EP7402-0057
39
Version: 1.3
4.5
Restoring the delivery state
To restore the delivery state for backup objects in ELxxxx terminals / EPxxxx- and EPPxxxx boxes, the CoE
object
Restore default parameters, SubIndex 001
can be selected in the TwinCAT System Manager (Config
mode).
Fig. 10: Selecting the Restore default parameters PDO
Double-click on
SubIndex 001
to enter the Set Value dialog. Enter the value
1684107116
in field
Dec
or the
value
0x64616F6C
in field
Hex
and confirm with OK.
All backup objects are reset to the delivery state.
Fig. 11: Entering a restore value in the Set Value dialog
Alternative restore value
In some older terminals / boxes the backup objects can be switched with an alternative restore
value:
Decimal value: 1819238756
Hexadecimal value: 0x6C6F6164
An incorrect entry for the restore value has no effect.