![Banner DXMR90-X1 Series Instruction Manual Download Page 49](http://html1.mh-extra.com/html/banner/dxmr90-x1-series/dxmr90-x1-series_instruction-manual_3746186049.webp)
May 09, 2023
DXMR90-X1 Series Controller Instruction Manual
49
File System and Archive Process
Update Your DXM Processor Firmware Using the Configuration Software
Specifications for the DXMR90-X1
Supply Voltage
12 V DC to 30 V DC
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Power Consumption
120 mA maximum at 12 V DC
Construction
Connector Body: PVC translucent black
Indicators
Amber: Power port 0
Amber: Modbus communications port 0-4
Green/amber: Ethernet communications
Red/amber/green: User-configurable LEDs
Connections
Five integral 5-pin M12 female quick disconnect
One integral 4-pin M12 male quick disconnect
One integral 5-pin M12 female D-Code quick disconnect
Application Note
When connecting external devices through the
DXMR90-X1, it
is important not to exceed maximum current limitations of 3.5
Amps
Communication Hardware (RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 1.2K, 2.4K, 9.6k, 19.2k (default), 38.4k, 57.6K, or
115.2K
Data format: 8 data bits, no parity, 1 stop bit
Communication Protocols
Modbus®
RTU, Modbus/TCP, EtherNet/IP™
,
and
PROFINET®
EtherNet/IP™ is a trademark of ODVA, Inc.
Modbus®
is a reg-
istered trademark of Schneider Electric USA,
Inc.
PROFINET®
is a registered trademark of PROFIBUS
Nutzerorganisation e.V.
Security Protocols
TLS, SSL, HTTPS
Environmental Ratings
For Indoor Use Only
IP65, IP67, NEMA 1, UL Type 1
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55
Hz, 1.0 mm amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 30G 11 ms dura-
tion, half sine wave)
Operating Conditions
–40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature
–40 °C to +80 °C (–40 °F to +176 °F)
Certifications
Banner Engineering BV
Park Lane, Culliganlaan 2F
bus 3, 1831 Diegem, BELGIUM
Turck Banner LTD
Blenheim House, Blenheim Court,
Wickford, Essex SS11 8YT, Great Britain
(CE/UKCA approval only applies to 2.4 GHz models)
Required Overcurrent Protection
WARNING: Electrical connections must
be made by qualified personnel in ac-
cordance with local and national electri-
cal codes and regulations.
Product Support and Maintenance
Chapter 8
© Banner Engineering Corp.
Summary of Contents for DXMR90-X1 Series
Page 4: ...Blank page 4...
Page 10: ...Blank page 10...
Page 18: ...Blank page 18...
Page 48: ...Blank page 48...
Page 55: ...LinkedIn Twitter Facebook 2023 All rights reserved www bannerengineering com...