DXMR90-X1 Series Controller Instruction Manual
38
Slots and Modules for DXM PROFINET
There are ten slots to accommodate the DXM Controller data.
Slots for input and output values
Values
Maximum Data Size
Input values
1440 bytes
Output values
1440 bytes
Slot 1 - Input (DXM --> PLC)
Module ID
Submodule ID
Module
Size (bytes)
Register Start
Register End
Direction
0x44
0x01
Banner IO-Link
Master Info
9
1
3
Input
6
6
123
123
It is important to note that the module placed in slot 2 corresponds to Port 1; the module placed in slot 3 corresponds to Port
2; the module placed in slot 4 corresponds to port 3. etc.
For the DXMR90-4K IO-Link Master device, slots 6 through 9 are unused.
If the IO-Link In/Out process data modules (all except digital input and output) are used, the attached IO-Link device
must
have PDI and PDO size less than or equal to the number of data bytes allowed in the module. Data transfers will not be ap-
plied otherwise.
For example, plugging in the 16/16 byte module to a slot corresponding to a device that has 22 bytes of PDO
results in an error. Process data sent from the PLC to DXM will not be applied.
Slots 2-9 (1 per IO-link port)
Module ID
Submodule ID
Module
Size
(bytes)
Register Start
Register End
Direction
0x45
0x01
IO-Link In/Out 32/32 Byte + Status
36
x001
x017
Bidirectional
x506
x507
46
x051
x067
x851
x859
0x46
0x01
IO-Link In/Out 16/16 Byte + Status
20
x001
x009
Bidirectional
x506
x507
30
x051
x059
x851
x859
0x47
0x01
IO-Link In/Out 8/8 Byte + Status
12
x001
x005
Bidirectional
Continued on page 39
◦
◦
◦
Status indicator bar
If the Application Status indicator is red, close and restart the DXM Configuration Tool, unplug and re-plug in
the cable and reconnect the DXM to the software.
If the Application Status indicator is green, the file upload is complete.
If the Application Status indicator is gray and the green status bar is in motion, the file transfer is in progress.
After the file transfer is complete, the device reboots and begins running the new configuration.