DXMR90-X1 Series Controller Instruction Manual
23
DXM Configuration Software to define the operational settings for both the Modbus RTU master ports 1–4 and the Modbus
RTU slave port 0.
Set the Master and Slave Port Parameters
The basic communications parameters for the RS-485 ports are set in the DXM Configuration Software and are saved in the
XML configuration file. Each port can have unique settings such as a unique baud rate, parity, timeout, and delays between
messages.
RTU Configuration screen for ports 0-4
◦
◦
◦
Define the
Port
settings to be compatible with the connected devices.
Verify the
Baud Rate
and
Parity
match that of the connected Modbus slave devices.
The
Timeout
controls how long the
DXMR90-X1
waits before determining a command failed to send. Set
based on the specific application requirements.
The
Delay between messages
defines the minimum wait time between resending another command. Set
based on the specific application requirements.
1.
Go to the
Register Mapping
›
RTU
›
RTU Configuration
screen.
RTU Configuration screen
a.
Go to the
Register Mapping
›
RTU
›
RTU Configuration
screen.
b.
Modify the
Port
settings as needed.
c.
To set the Modbus Slave parameters for Port 0, go to
Settings
›
System
›
Slave Port 0 Settings
.
2.
The Internal Slave ID is the Modbus ID that an external Modbus Master will access to read/write to the local registers
on the
DXMR90-X1.
© Banner Engineering Corp.