To send email, you must supply the SMTP Server, Server Port, and login credentials.
The default SMTP port is 25 but may need to be adjusted for Ethernet-based networks. Note that many facilities block port
25. Port 587 is another common SMTP submission port.
The SMTP password is not stored in the XML configuration file, but on the
DXMR90-X1. After the password is entered, click
on
Send SMTP Password
to send it to the
DXMR90-X1. The password is stored in non-volatile memory, so reboot
the
DXMR90-X1
to recognize the new password.
When using a GMail server, select
Situational encryption
and
Enable SMTP authentication. GMail may notify you that you
must allow access for less secure apps in your email settings.
For other email servers, the parameters may vary and will require information from the provider.
Email settings
At the bottom of the screen, define the recipient to receive emails. These recipients selected in the threshold definition for
sending alert messages.
Define Threshold Rules for Email
To define a threshold, go to
Local Registers
›
Action Rules
›
Thresholds
.
Depending upon which recipients are defined, select the appropriate email or SMS checkbox for the threshold rule (un-
der
Email/SMS on state transition
). When the threshold rules goes active or inactive, an email is generated.
For more information on how to set up threshold rules, refer to the DXM Configuration Software Instruction Manual (p/
).
Push Retries
Ethernet
—The
DXMR90-X1
can be configured to send register data packets to a webserver. When the Ethernet communica-
tions path is not operating, the
DXMR90-X1
retries the send procedure. With an Ethernet-based network connection,
the
DXMR90-X1
retries a message five times. The five retry attempts immediately follow each other. After all attempts are ex-
hausted, the register data packet is lost. At the next scheduled time, the
DXMR90-X1
attempts to send only the new data.
Any past data that the DXMR90 was unable to push is lost and cannot be recovered. Using SSL on Ethernet will have no re-
tries.