HOW TO FIND THE CAUSES OF IMPROPER WORKING AND HOW TO RECTIFY THEM
TYPE OF IRREGULARITY
POSSIBLE CAUSE
SOLUTION
Burner does not start.
(the appliance does not perform the
ignition program)
1) Thermostats (boiler/room) or pressure
switches open
2) Photoresistant-cell in short circuit
3) No voltage with an open isolating switch or
with a tripped max. contactor switch or line
voltage failure
4) Thermostat line not wired according to dia-
gram or open thermostats
5) Failure inside the control-box
1) Increase their value or wait until they activate
due to natural reduction of the temperature
or pressure
2) Replace it
3) Activate switches or wait for power to return
4) Check connections and thermostats
5) Replace it
Defective flame with sparks.
1) Atomizing pressure too low
2) Too much combustion air
3) Dirty or worn nozzle
4) Water in the fuel
1) Reset at proper value
2) Reduce combustion air flow
3) Clean or replace it
4) Remove it from the tank using a suitable pump.
(Never use the burner pump for this job)
Flame badly shaped with smoke and
soot.
1) Insufficient combustion air flow
2) Dirty or worn nozzle
3) Combustion chamber unsuitably designed
or too small
4) Nozzle capacity too low with respect to com-
bustion chamber volume
5) Unsuitable refractory coating (excessive
reduction in gap for flame)
6) Boiler or chimney ducts clogged
7) Atomization pressure low
1) Increase combustion air
2) Clean or replace it
3) Reduce the nozzle delivery rate to suit the
combustion chamber capacity (obviously the
thermal power will be lower than the required
one) or replace the boiler
4) Replace the nozzle, increasing its capacity
5) Modify ensuring that the instructions of the
boiler manufacturer are carefully followed
6) Clean them
7) Raise pressure to the prescribed value
Defective pulsating escaping flame or
receding from the combustion orifice.
1) Excessive draft (only if
there is a suction unit to the chimney)
2) Dirty or worn nozzle
3) Water in the fuel
4) Dirty disk
5) Excess combustion air
6) Air passage between disk and blast tube
1) Adjust the suction fan speed by changing the
pulley diameter
2) Clean or replace it
3) Remove it from the tank with a suitable pump
(never use the burner pump for this job)
4) Clean it
5) Reduce combustion air
6) Rectify the position of the blast tube.
Corrosion inside the boiler.
1) Boiler operating temperature too low (lower
than the dew point)
2) High sulphur content in the fuel Smoke tem-
perature too low (below 130 °C).
1) Increase the operating temperature
2) Change grade of fuel if the boiler allows it.
Soot at the chimney exit.
1) Excessive cooling (below 130°C) of smoke
before exit outflow, for an outside chimney not
adequately heat insulated or cold air infiltration
1) Improve insulation and close any gap letting
cold air in.
Summary of Contents for TBML 80 MC
Page 2: ......
Page 33: ...31 34 0006081545_201305 ENGLISH WIRING DIAGRAM...
Page 34: ...32 34 0006081545_201305 ENGLISH...
Page 35: ...33 34 0006081545_201305 ENGLISH...
Page 67: ...31 34 0006081545_201305 ESPA OL ESQUEMA EL CTRICO...
Page 68: ...32 34 0006081545_201305 ESPA OL...
Page 69: ...33 34 0006081545_201305 ESPA OL...
Page 101: ...31 34 0006081545_201305 ITALIANO T RK E DEUTSCH SCHALTPLAN...
Page 102: ...32 34 0006081545_201305 ITALIANO T RK E DEUTSCH...
Page 103: ...33 34 0006081545_201305 ITALIANO T RK E DEUTSCH...
Page 135: ...31 34 0006081545_201305 T RK E ELEKTR K EMASI...
Page 136: ...32 34 0006081545_201305 T RK E...
Page 137: ...33 34 0006081545_201305 T RK E...
Page 140: ...2 34 0006081545_201305 5 8 SUNTEC 14 15 LME 73 16 17 19 19 21 21 22 24 25 26 28 31...
Page 141: ...3 34 0006081545_201305 BALTUR...
Page 142: ...4 34 0006081545_201305 3 2 RC B...
Page 146: ...8 34 0006081545_201305 5 6 0002934670 3 2 4 1 7...
Page 147: ...9 34 0006081545_201305 10 11 12 000293640 65 80...
Page 148: ...0002911090 10 34 0006081545_201305 EN 676 1 2 3 4 5 6 7 1200 8 9 10 11 12 13...
Page 154: ...16 34 0006081545_201305 LME 73 1 EK EK 2 1 2 BCI AZL2 1 TW...
Page 157: ...19 34 0006081545_201305 O K1 9 2800 9 1 2 1 2 1 1 1 000293 1 1 1 2 2 2...
Page 158: ...13 12 acc_reg001 psd TBML 80MC 003 psd 20 34 0006081545_201305 2 13 2 2 CO2 10 13 2...
Page 159: ...1 7 8 2 3 4 5 6 10 9 Display TBML 80 PN GAS L 21 34 0006081545_201305 1 2 3 4 5 3 7 8...
Page 161: ...23 34 0006081545_201305 1 8 1 1 2 LME 73 200 500 1 3 50 C 5 10 C...
Page 164: ...26 34 0006081545_201305 TBML 80 MC 1 2 3 4 5 6 7 8 9 10 4 0002936380...
Page 169: ...31 34 0006081545_201305...
Page 170: ...32 34 0006081545_201305...
Page 171: ...33 34 0006081545_201305...
Page 174: ...2 34 0006081545_201305 5 8 10 11 SUNTEC 14 15 LME 73 16 17 19 19 21 21 22 24 25 26 28 31...
Page 175: ...3 34 0006081545_201305 a b c a b c d e f g...
Page 176: ...4 34 0006081545_201305 3mm 2 RC a b c d e a b a b c d...
Page 180: ...8 34 0006081545_201305 6 5 0002934670 3 2 7 4 1...
Page 181: ...9 34 0006081545_201305 M 10 11 4 12 0002936400 DN65 DN80...
Page 182: ...0002911090 10 34 0006081545_201305 E N 6 7 6 1 2 3 4 5 6 7 1200 kW 8 9 10 11 12 13...
Page 188: ...16 34 0006081545_201305 LME 73 1 EK LED EK LED 1 2 BCI AZL2 1 LED TW...
Page 191: ...19 34 0006081545_201305 O K1 9 1 2 2800 rpm 9 000293 13 CO2 10 13...
Page 192: ...13 12 acc_reg001 psd TBML 80MC 003 psd 20 34 0006081545_201305...
Page 193: ...1 7 8 2 3 4 5 6 10 9 Display TBML 80 PN GAS L 21 34 0006081545_201305 1 2 3 L E D 3 4 5 3 7 8...
Page 195: ...23 34 0006081545_201305 UV UV UV UV UV UV LME 73 200 500 1 1 50 C 5 10 C...
Page 198: ...26 34 0006081545_201305 TBML 80 MC 1 2 3 4 5 6 7 8 9 10 4 0002936380...
Page 199: ...27 34 0006081545_201305 TBML 120 160 200 MC 1 2 3 4 5 6 7 8 9 3 TBML 200 MC 10 4 0002936380...
Page 203: ...31 34 0006081545_201305...
Page 204: ...32 34 0006081545_201305...
Page 205: ...33 34 0006081545_201305...
Page 207: ......