Figure 39. Example Configuration. LIN Main Schedule Table #1
Finally, start the LIN bus communication by configuring the
LIN Common
function block. Set:
Node Type
to
Master
and
Baud Rate
to
10417 bit/sec
.
Tick Time
should be left at the default
value of
10 ms
.
Figure 40. Example Configuration. LIN Common
The LIN bus is now running. Configure CAN bus input signals. All three input signals will parse
one CAN message. Start from
CAN
Receive
#1
and configure it as IntensityRed signal. The