Address 092 enables ‘Answer Now’ (answers remote computer after 1 ring). The user attending
the control panel can reduce the number of rings before answer to one ring.
Answering machine bypass
In case the alarm panel connected with fax or answering machine on the same telephone line (not
recommended) enable the Answering Machine Bypass or Answer Now features (otherwise
connection is impossible).
To enable the feature:
1. Program 7 at address 076
2. Program at least 20 seconds at address 097 (Ring Time Out)
Now dial to the control panel, count at least three rings and disconnect, dial again immediately –
the panel will answer at first ring.
When Answering Machine Bypass enabled, the control panel will answer at first ring if:
- There was a pause of at least 10 seconds from last ring
- The panel already counted at least three rings before the pause
- Number of rings to answer (at address 091) is less than 20
Notice:
The panel will answer (in a normal mode) if there is no pause and the rings counted exceed (or
equal) the number programmed at 091.
Step 5: Disconnecting
When download completed, disconnect the PC from the remote Control Panel by selecting
‘Disconnect’ from the main menu.
Control panel status after disconnection:
A remote PC might connect the control panel while unattended by the owner, the following must
be taken in account:
The panel will always ARM (if told so by the remote) regardless of the status of zones. That
means that currently open zones will not prevent the panel from Arming (not possible with the
keypad).
After a remote connection the history log is not cleared.
For Belgian standard user: If the alarm was caused by ‘Tampering’ the zones, and the ‘Lock
System after Tampers Alarm’ feature was programmed, the system will remain locked while it is
Armed.
If the control panel was contacted after an alarm, and then Armed or Disarmed, the last events
are not cleared. Thus, even after system disarmed by the remote PC, the keypad still displays the
zones that caused previous alarms and the status LED blinks (although there are currently no open
zones). Pressing the Reset (hold down '9') key will clear these alarms.
Instruct the owner to clear the history log from time to time. This will keep the history log
reasonably short (the maximum event number is 250) and will cut down the download time.
Zone Description Transfer
Starting EasyLoad version 3.00 Zones and Logo texts are possible to Upload/Download via PC.
Texts uploaded automatically to the keypads after communication is closed.