Enable Siren Test upon Arming
- Short beep sound for siren test upon arming, indicating that
the system armed and siren is OK. To enable this feature (Siren Test upon Arming), enter value
‘1’ in address 070.
Enable SLO 1 for Smoke Detector
Reset
- After the smoke alarm is triggered, reset is required.
Pressing key ‘9’ activates SLO 1, which shortly disconnects smoke detector power (via optional
relay) and resets automatically. Address: 071- 3.
Entry Delay 1 and 2
- To enable two different entry delay periods, program-selected zone(s) for
Entry Delay 1, and other zones for Entry Delay 2. To cancel entry delay, hold - down key 4 before
Arming.
Entry Delay 1 maximum delay time is 99 seconds, and Entry Delay 2, up to 396 seconds (see
addresses 060 and 061).
Addresses: 104, 106, 108, 110.
Entry/Exit Follower Zone
- Reacts instantly upon detection without previous triggering of
delayed zone. Exit delay affects follower zones. Follower zone acts as delayed zone during exit
delay and after entering via delayed zone. Try to avoid installing magnetic switches for protection
of a follower zone. (Use magnetic switch in delayed zone only for entry/exit door).
Address: 112-115.
Erase ‘Follow-Me‘ Number upon Disarming
- After disarming the system, the Follow-Me
number is deleted. If ‘Erase’ feature is not programmed, the ‘Follow-Me’ number will be stored in
the system memory as the first Dialer number.
Address: 071-1.
Exit Delay
- Determines the delay period (for delayed or follower zones) before zone becomes
active. Countdown starts upon system arming. Maximum exit delay is 396 seconds.
Address: 062.
Exit Delay when Delayed Zones Clear -
Enables system Arming only when all delayed zones
are clear. Exit Delay will start the countdown. Applicable when long or variable exit delay is
required.
Address: 072.
Fire Zone -
Zone programmed for connection of fire or smoke detector. Alarm sounded in both
Armed and Disarmed modes. Activate the Fire LED. If Fire zone remains troubled after disarming
the system a warning buzzer will sound after 10 seconds from disarming (allows the user to repair
or bypass the troubled zone). After another 10 seconds, the alarm is on.
The siren sounds different at 24H zone alarm (not same as burglary alarm).
Address: 120-123.
Fast Response Zone
- Fast Response time of 100 ms (standard response time is 750 ms).
Use Fast Response zone for connection of shock (inertia) or beam type detectors. The response