16
•
Speaker siren issues a multiple-tone alarm. Use 8 to 16 ohm speaker siren, 14 watts
minimum.
•
Bell mode (sounder that works on 12V DC) is available via programming.
•
Enclose the outdoor siren in a metal box tamper-switch protection.
•
Protect siren or bell box with tamper-switch connected to a 24H zone.
•
The control unit contains two siren outputs, for internal and external siren, individually
protected by fuses.
•
If Siren mode selected, use speaker type siren with a minimum power of 15W, 8 Ohms
impedance. Enclose the outdoor siren in a metal housing, with anti-tamper switch
protection.
•
In Siren mode, install only speaker-type sirens, which DO NOT contain sound driver or
electronic modules.
•
The alarm issued by the Siren (not Bell mode) differs according to the type of zone.
•
‘Bell Mode‘ is default-set at factory. Bell converts Siren outputs into 13.6 VDC outputs (no
sound is issued). Bell mode is applicable for driving self-powered sirens or bells, or
combined sirens and strobes.
•
In Bell mode, connect
only
Bell or
sirens that contain a 12V sound electronic driver
module. Bella sirens are compatible and feature high sound level at very low current use.
•
Self-contained Bell mode is programmable (address 071). This mode allows connection of
Bells or Sirens that require 12V at ideal and 0V during alarm. The Bell output voltage
regulated at about 13.6V. For self-contained siren, it is recommended to use Av-Gad Bella 2
or Bella 3 siren, both with Xenon strobe light.
Warning!
Output power for each Bell should not exceed 0.7A (total Bell output is 1.4A).
•
Contact manufacturer's consultant before connecting higher power loads.
•
To connect self-contained sirens, Bells, and inner-oscillating sirens, refer to address 072;
see Bell mode.
•
Contact manufacturer's consultant before connecting higher power loads.
3.2
Remote Indication Terminals
Indication Application
ON
(-V) on closing (Arming)
OUT 1 (A1)
Programmable. (-V) during alarm from the programmed zone or
event (tamper alarm or panic)
OUT 2 (A2)
AV-2016
only Programmable. (-V) during alarm from the programmed zone or
event (reset, tamper alarm or panic)
SLO Output
Programmable. (-V) during alarm from the programmed zone
Resets only upon disarming
(SLO is a non-timed output).
Most useful for strobe light connection.
SLO 1 Output
Programmable. (-V) during Smoke reset or Code 7 entry