DFMS editing window – continued
1
Extension Configuration
In this window the user declares the number of connected extensions. The maximum of 5 20-button extensions can be
connected to the microphone. Respectively to the selected number of extensions, the configuration window will extend to
include the field for additional button name editing and ability to assign a function using the
Events
button. The extended
editing field is shown below:
2
Fireman Microphone Configuration
The fireman microphone
PTT button
function window. Apart from the
PTT
– Push to talk mode in the
Mode
option, there
is a possibility to select
LOCK
, i.e. having pressed the PTT button, the microphone is active for the time defined in the
Lock
Timeout
window. The maximum microphone activation time is 60 seconds.
The
Start Gong
option – this enables the gong having pressed the PTT button;
End Gong
will be activated after
the PTT button is released.
3
Network Settings
This is the address which will be assigned to a physical device having loaded a configuration into the system. Changing IP
addresses assigned by the configurator is not recommended.
4
RS485 Settings
The RS485 port allows the system to communicate with external devices. However, this requires selecting the appro-
priate protocol from the list.
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...