131
The time is determined in minutes / The time interval [15 ... 300 minutes]
Default state – checkbox enclosed, active function
Default activation time: 60 minutes
AutoStandby
function is available in the
Basic Configuration
:
Each attempt of audio broadcasting while
Standby
is active causes:
» exit from
Standby
to the
Normal
mode (when operating on the primary power source), regardless on the priority of a message ;
» exit from
Standby
mode to the
BattMode
(when there is lack of primary power supply) only when messages will have
Service
/
Emergency
priority.
The maximum duration of the activation process of exit from
Standby
mode to broadcasting message is shorter than 500 ms.
Because the function has been implemented in Phase 1 of AutroVoice miniVES development and its activation is dynamic
(
Zone selection
then pressing
Power Save
button) there is need to change the way of its implementation from the dynamic to
static (PA zones strictly defined in the configurator are to be deactivated / activated by friendly
Power Save
features.
Diagram of transition
Normal
mode –
Battery
mode –
Standby
mode is shown below:
Normal
(230 V Powered)
BattMode
(Battery Powered)
Standby
(230 V or
Battery Powered)
Condition:
Restored Power 230 VAC
TODO:
Deactivate PowerSave
(Restore Saved Audio Matrix)
Condition:
Lost Power 230 VAC
TODO:
Activate PowerSave
(Save and Mute Active
Audio Matrix General, BGM)
Condition:
No Active Audio Matrix (Emergency/Service)
No Alarm Mode
Trigger:
Activate PowerSave
(by Timer, Logical Input, Key, Auto Power-Save)
TODO:
Save and Mute Active Audio Matrix: General, BGM
Condition:
No Alarm Mode
No Active Emergency/Service Audio Matrix
Condition:
230 VAC Present
Trigger:
Created Audio Matrix (Emergency/Service/General/BGM)
Power Save Off (Timer, Logical Input, Key)
TODO:
Restore Saved Audio Matrix
Condition:
230 VAC
Trigger:
Created Audio Matrix (Emergency/Service)
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...