96
COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
Paste to all
function allows to copy EQ settings to all outputs available in the control unit. To do so select
Copy
to save the
settings of the filters and then select
Paste to all
to propagate all filters settings to all outputs.
Setting the level of threshold below 0 dB activates the audio limiter. Signal level exceeding threshold is indicated by the red
color in the
Limiter
status. Green indicates that the output is below the threshold. In practice activation of audio limiter means
that above a threshold, output signal is not increasing, regardless of what value the input signal reaches. The
Limiter
allows
to protect the system amplifiers from clipping the signal peaks and sharp reduction in high-level transients without affecting
the essential content sound material.
Signal Level Meter
is only active in on-line mode. The maximum level shown on the indicator corresponds to the
voltage of 1 V RMS output codec.
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...