Basic Configuration editing window – continued
1
Disable CPU-OFF
This option in it’s default setting (on) disables the central processing unit bypass mode. In order to activate the CPU-Off
function accessible from the ABT-DFMS and AutroVoice miniVES front panel by a dedicated switch, uncheck this box.
2
AutoStandBy
Enabling this mode in the AutroVoice miniVES system results in:
Ű limiting current draw from the batteries when in emergency power mode;
Ű limiting heat generated by the amplifier modules during standard operation mode.
The system enters
Standby
mode when no audio has been transmitted through the system for the time set in the software.
The time is set in minutes in the 15 to 300 bracket. The default state of this option is active with the default time set to
60 minutes.
For more details see the appendix section.
3
Defining IP address pool to assign system devices
This window shows the range the configurator uses to assign IP addresses to all programmable elements of the AutroVoice
miniVES system in the internal system network. It is possible to change the settings of the assigned pool, however it is not
recommended by the manufacturer. The settings should be changed prior to adding the first device to the workspace.
4
System firmware update field
Every software version has a corresponding firmware that is uploaded to the Central Units, fireman microphones and zone
microphones. Every time a new configuration is uploaded to the system, the configurator software compares firmware
versions. If a different firmware version than the one in the configurator is detected, it will be overwritten. It’s possible to
load a different (newer) firmware version than the one supplied with the software. In order to do so you must manually
set the new firmware path by clicking
browse
. The new firmware path will appear in the
path
window. In order to upload
the new firmware to the system, click
change
– this will display the new firmware version in the
FW version to upload
field.
For more details see the Appendix section.
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...