121
Display Text
Activation of the display text function opens a dialogue box on a selected and available GUI screen in the system and prompts
display of the text entered into the
Text to display
window.
Failure Accept
This is a global function which mutes the acoustic signalization of a failure within the entire system. The moment any failure occurs
in the system, the yellow LED on the failure accept button blinks additionally on each element of the system equipped with a GUI,
the buzzer goes off as well. Having accepted the failure, the yellow LED is lit and the persistent acoustic signal stops.
Failure Delete
Deleting a failure is a global function affecting the entire system. The function is active only if and when the system is in the failure
status. Activation of the
Failure delete
results in resetting of the system element in which the failure was detected, and then
running the system test procedure.
General
This function combines three main functionalities of the AutroVoice miniVES system:
Scenarios
,
Matrices
and
logical
outputs
,
alongside an access to RGB LED behaviour programming on zone microphones. The
General
function enables to
assign to a logical input or a button of any defined scenario, matrix combination, alongside a possibility to define system LED and
logical output activation in an individual way.
If in the
General
function, the icon
is selected, then this function is assigned a matrix. Activation of the general function enables
to activate or deactivate one or multiple matrices defined in the system, using one logical input or button on a zone / fireman
microphone. Each matrix can have an individual activation mode assigned to it –
start
/
stop
/
toggle
.
If in the
General
function, the icon
is selected, then this function is assigned a scenario. Activation of the general function
enables to activate or deactivate scenarios using one logical input or button on a zone / fireman microphone. Each scenario can
have an individual activation mode assigned to it –
start
/
stop
/
toggle
.
If in the
General
function, the icon
is selected, then this function is assigned a selected logical / relay output. The figure below
presents the options, as available:
Component
– enables to select an output card or fireman microphone from the list, a communications card containing
the output we want to use.
Summary of Contents for AutroVoice miniVES 2001
Page 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 147: ...147 15 Certificates...
Page 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Page 153: ...153...
Page 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Page 155: ...155...