DL205 Installation and I/O Manual, 2nd Edition
3–50
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08AD-2 8-Channel Voltage Analog Input Module
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
Includes circuitry to automatically detect broken or open transmitters.
Number of Channels
8, single ended (1 common)
Input Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 VDC
Resolution
12 bit (1 in 4095) uni-polar
13 bit (-4095 to 4095) bi-polar
Active Low-pass Filtering
-3dB at 200 Hz,
(-6dB per octave)
Input Impedance
>20 M
Absolute Maximum Ratings
-75 to +75 VDC
Converter Type
Successive approximation
Conversion Time (PLC
Update Rate)
1 channel per scan maximum (D2-230 CPU)
8 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Linearity Error (End to End)
±1 count (0.025% of full scale) maximum
Input Stability
±1 count
Full Scale Calibration Error
(offset error not included)
±3 counts maximum
Offset Calibration Error
±1 count maximum (0V input)
Step Response
1 ms to 95% of F.S. change
Maximum Inaccuracy
±.1% @ 77ºF (25ºC)
±.3% 32º to 140ºF (0º to 60ºC)
Accuracy vs.Temperature
±50 ppm/ºC maximum full scale
(including max. offset change of 2 counts)
Digital Input Points Required
16 (X) input points,
(12 binary data bits, 3 channel ID bits, 1 sign bit,
1 diagnostic bit)
Base Power Required 5VDC
100 mA
External Power Supply
5 mA maximum, +10 to +30 VDC
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON