D2–08TR, Relay Output
0
2
4
6
8
Poin
ts
0.5A / P
t
.
COM
OUTP UT
To LE D
In
t
e
r
nal mo
d
ule ci
r
cui
tr
y
6.3A
5--240 VAC
L
5--30 VDC
1A / P
t
.
C
C
0
1
2
3
4
5
6
7
In
t
e
r
nally
connec
t
e
d
L
L
L
L
L
L
L
L
5--240 VAC
5--30 VDC
0
10
20
30
40
50 55
Ambien
t
Tempe
r
a
t
u
r
e (°C/°F )
32
50
68
86
104
122131
C
°
F
°
C
C
0
4
1
5
2
6
3
7
5-240VAC
1A50/60Hz
D2--08TR
OUT
RELAY
D2--08TR
0
1
2
3
4
5
6
7
L
L
5--30VDC
5mA--1A
De
r
a
t
in
g
Cha
rt
Outputs per Module
8
Outputs Points Consumed
8
Commons per Module
1 (2 I/O terminals)
Output Type
Relay, form A (SPST)
Operating Voltage
5-30 VDC; 5-240 VAC
Peak Voltage
30 VDC, 264 VAC
ON Voltage Drop
N/A
AC Frequency
47 to 60 Hz
Minimum Load Current
5mA @ 5VDC
Max Load Current (resistive)
1A/point; 4A/common
Max Leakage Current
0.1 mA @265 VAC
Max Inrush Current
Output: 3A for 10 ms
Common: 10A for 10 ms
Base Power Required 5VDC
250 mA
OFF to ON Response
12 ms
ON to OFF Response
10 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
3.9 oz. (110g)
Fuses
One 6.3A slow blow, replaceable
Order D2-FUSE-3 (5 per pack)
Chapter 3: I/O Wiring and Specifications
3–38
DL205 Installation and I/O Manual, 2nd Edition
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Typical Relay Life (Operations)
Voltage/Load
Current
Closures
24 VDC Resistive
1A
500k
24 VDC Solenoid
1A
100k
110 VDC Resistive
1A
500k
110 VDC Solenoid
1A
200k
220 VAC Resistive
1A
350k
220 VAC Solenoid
1A
100k