DL205 Installation and I/O Manual, 2nd Edition
3–48
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
This module can be powered by either a 12 VDC or 24 VDC power supply, and is a direct
replacement for F2-04AD-2L modules.
Number of Channels
4, single ended (1 common)
Input Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 V
Resolution
12 bit (1 in 4096)
Active Low-pass Filtering
-3 dB at 80 Hz, 2 poles (-12 dB per octave)
Input Impedance
>20 M
Absolute Maximum Ratings
-75 to +75 VDC
Converter Type
Successive approximation
Conversion Time
(PLC Update Rate)
1 channel per scan maximum (D2-230 CPU)
4 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Linearity Error (End to End)
±1 count (0.025% of full scale) maximum
±2 counts maximum (bi-polar)
Input Stability
±1 count
Full Scale Calibration Error
(offset error not included)
±3 counts maximum
Offset Calibration Error
±1 count maximum (0V input)
Maximum Inaccuracy
±.1% @ 77ºF (25ºC)
±.3% 32º to 140ºF (0º to 60ºC)
Accuracy vs.Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change )
Digital Input Points Required
16(x) input points
(12 binary data bits, 2 channel ID bits)
Base Power Required 5VDC
110 mA
External Power Supply
5 mA maximum, +10 to +30 VDC
Operating Temperature
32º to 140ºF (0 to 60ºC)
Storage Temperature
-4º to 158°F (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
F2-04AD-2 4-Channel Voltage Analog Input Module
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).