DL205 Installation and I/O Manual, 2nd Edition
3–70
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08DA-2 8-Channel Voltage Analog Output Module
Number of Channels
8, single-ended, 1 common
Output Ranges
0 to 5V, 0 to 10V
Resolution
12 bit (1 in 4096)
Output Type
Voltage sourcing
Digital Output Points
Required
16 (Y) output points
(12 binary data bits, 3 channel ID bits,
1 output enable bit)
Base Power Required 5VDC
60 mA
External Power Supply
21.6-26.4 VDC, 140 mA (outputs fully loaded)
Peak Output Voltage
15 VDC
(clamped by transient voltage suppressor)
Load Impedance
1-10 k
Load Capacitance
0.01 µF maximum
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
8 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Conversion Settling Time
400 µs maximum (full scale change)
4.5 ms to 9ms for digital out to analog out
Linearity Error (end to end)
±1 count (±0.025% of full scale) maximum
Full Scale Calibration Error
±12 counts max. unipolar @ 25ºC (77ºF)
Offset Calibration Error
±3 counts max., unipolar @ 25ºC (77ºF)
Accuracy vs. Temperature
±57 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
±0.3% @ 25ºC (77ºF)
±0.45% @ 0-60ºC (32-140ºF)
Operating Temperature
0º to 60ºC (32º to 140°F)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).