DL205 Installation and I/O Manual, 2nd Edition
3–51
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-08AD-2 8-Channel Voltage Analog Input
+24V
CH1+
CH2+
CH3+
CH4+
CH5+
CH6+
CH7+
CH8+
IN
ANALOG
F 2--08AD--2
0V
10-30VDC
5mA
ANALOG IN
0-5,0-10VDC
+/-5,+/-10VDC
AD
C
Voltage
Trans mitter
Voltage
Trans mitter
Voltage
Trans mitter
Voltage
Trans mitter
CH1
CH3
+
CH5
+
CH7
+
0 VDC
24VDC
+
-
CH2
CH4
+
CH6
+
CH8
+
CH1
CH2
CH3
CH4
24VDC
Analog Multiplexer
+
+
0V
3-wire
2-wire
4-wire
3-wire
+
-
+
+
+
+
+
+
-
-
-
-
Note 1: Shields should be grounded at the signal source.
Note 2: Connect all external power supply commons.
Note 3: Connect unused channels (CH5+, CH6+, CH7+, CH8+ in this example) to 0VDC.