D2–12TA, AC Output
Addres s es Us ed
Yes
Yes
Yes
Yes
Yes
P oints
Yn+0
Yn+1
Yn+2
Yn+3
Yn+4
Yn+5
Yes
Us ed?
No
Yn+6
Yn+7
No
n is the starting address
Yes
Yes
Yes
Yes
Yes
P oints
Yn+10
Yn+11
Yn+12
Yn+13
Yn+14
Yn+15
Yes
Us ed?
No
Yn+16
Yn+17
No
Optical
COM
Is olator
OUTP UT
To LE D
Internal module circuitry
3.15A
15--132
L
0
3
6
9
12
Points
VAC
250mA / Pt.
300mA / Pt.
0
1
2
3
5
NC
NC
NC
0
1
2
3
CB
4
5
NC
NC
CA
4
L
L
L
L
L
L
L
L
L
L
15--132 VAC
15--132 VAC
0
10
20
30
40
50 55
Ambient Temperature (˚C/˚F )
32
50
68
86
104
122131
C
˚
F
˚
A
B
15--132VAC
10mA--0.3A
D2--12TA
OUT
18--110
D2--12TA
VAC
0
1
2
3
4
5
CA
4
5
CB
4
5
3
2
1
0
3
2
1
0
50/60 Hz
L
L
Derating Chart
Outputs per Module
12
Outputs Points Consumed
16 (four unused, see chart below)
Commons per Module
2 (isolated)
Output Type
SSR (Triac)
Operating Voltage
15-132 VAC
Peak Voltage
132 VAC
ON Voltage Drop
< 1.5VAC (>50mA)
< 4.0VAC (<50mA)
AC Frequency
47 to 63 Hz
Minimum Load Current
10 mA
Max Load Current
0.3A/point; 1.8A/common
Max Leakage Current
2mA (132 VAC, 60 Hz)
Max Inrush Current
10A for 10 ms
Base Power Required 5VDC
350 mA
OFF to ON Response
1 ms
ON to OFF Response
1 ms + 1/2 cycle
Terminal Type (included)
Removable; D2-16IOCON
Status Indicator
Logic side
Weight
2.8 oz. (80g)
Fuses
(2) 1 per common
3.15A slow blow, replaceable
Order D2-FUSE-1 (5 per pack)
Chapter 3: I/O Wiring and Specifications
3–36
DL205 Installation and I/O Manual, 2nd Edition
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D