DL205 Installation and I/O Manual, 2nd Edition
3–64
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
This module requires a 24 VDC user power supply for operation. See the F2-02DA-2L on
the next page if you want to use a 12 VDC supply. All other specifications are the same.
Number of Channels
2
Output Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 V
Resolution
12 bit (1 in 4096)
Output Type
Single ended, 1 common
Digital Output Points
Required
16 (Y) output points
(12 binary data bits, 2 channel ID bits)
Peak Output Voltage
15 VDC (clamped by transient voltage
suppressor)
Load Impedance
2000
minimum
Load Capacitance
.01 µF maximum
PLC Update Rate
1 channel per scan maximum D2-230 CPU
2 channels per scan maximum (D2-240, D2-
250(-1) and D2-260 CPUs)
Linearity Error (end to end)
±1 count (0.025% of full scale) maximum
Conversion Settling Time
5µs maximum (full scale change)
Full Scale Calibration Error
(offset error included)
±12 counts max. unipolar @ 77ºF (25ºC)
±16 counts max. bipolar @ 77ºF (25ºC)
Offset Calibration Error
±3 counts max., unipolar @ 77ºF (25ºC)
±8 counts max., bipolar @ 77ºF (25ºC)
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
+0.3% unipolar ranges @ 77ºF (25ºC)
±0.45% unipolar ranges >77ºF (25ºC)
±0.4% bipolar ranges @77ºF (25ºC)
±0.55% bipolar ranges >77ºF (25ºC)
Base Power Required 5VDC
40 mA
External Power Supply
18 to 30 VDC, 60 mA (outputs fully loaded)
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
F2-02DA-2 2-Channel Voltage Analog Output Module
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).