DL205 Installation and I/O Manual, 2nd Edition
3–59
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-02DA-1L 2-Channel 4-20mA Analog Output
OV
+
--
12 VDC
S ee
0 VDC
+12 VDC
N/C
N/C
N/C
N/C
NOTE 1
70mA + 20mA
for each loop
+
V
CH1--
CH1+
CH2--
CH2+
NC
NC
NC
NC
10--15 VDC
70mA
F 2--02DA--1L
OUT
ANALOG
F 2--02DA--1L
2CH
ANALOGOUT
4--20mA
0V
CH1--
CH2--
CH1+
CH2+
Current s inking
Ch 1
Current s inking
Ch 2
DC
to
DC
C
onve
rte
r
+5V
+15V
0V
--15V
D to A
Converter
D to A
Converter
12
Ch 1 load
250
Ω
typical
Ch 2 load
250
Ω
typical
Internal
Module
Wiring
Transient protected
precision digital to analog
converter output circuits
Typical User Wiring
Maximum user load is dependent upon loop power supply.
Loop power supply
Load range (ohm)
15 VDC
0 to 450
12 VDC
0 to 300
10 VDC
0 to 200
NOTE 1: Shields should be connected to the 0V of the module or the OV of the P/S.
NOTE 2: Unused current outputs should remain open (no connections) for minimum power consumption.