Chapter 3: Configuration and Parameters
Page 3–69
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
p
arameTer
d
eTails
– “l
og
” m
enu
of
p
arameTers
(
ConTinued
)
Each SR55 is tested at the factory, and each unit may have a brief log history from this
testing.
P19.2 –
Last Peak Stop Current -2
Type:
Description:
Read Only
Displays the peak current of the last successful stop -2.
Range:
Modbus Decimal Value:
Default:
• Peak Current: 0A – 10,000A
• Peak Current Time: hh:mm:ss
• linear scale (1 = 1mA)
Current (A) = (Value / 1000)
• Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
• 0A
• GMT
Modbus Address:
Modbus Format:
• Peak Current: 39044/39045 ( 9884/9885 hex )
• Peak Current Time: 39110/39111/39112 ( 98C6/98C7/98C8 hex )
• 32-bit unsigned
• 6 Bytes
Touchscreen Menu Path:
Home → Log → Stop Current Log → Last Peak Stop Current -2
P19.3 –
Last Peak Stop Current -3
Type:
Description:
Read Only
Displays the peak current of the last successful stop -3.
Range:
Modbus Decimal Value:
Default:
• Peak Current: 0A – 10,000A
• Peak Current Time: hh:mm:ss
• linear scale (1 = 1mA)
Current (A) = (Value / 1000)
• Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
• 0A
• GMT
Modbus Address:
Modbus Format:
• Peak Current: 39046/39047 ( 9886/9887 hex )
• Peak Current Time: 39113/39114/39115 ( 98C9/98CA/98CB hex )
• 32-bit unsigned
• 6 Bytes
Touchscreen Menu Path:
Home → Log → Stop Current Log → Last Peak Stop Current -3
P19.4 –
Last Peak Stop Current -4
Type:
Description:
Read Only
Displays the peak current of the last successful stop -4.
Range:
Modbus Decimal Value:
Default:
• Peak Current: 0A – 10,000A
• Peak Current Time: hh:mm:ss
• linear scale (1 = 1mA)
Current (A) = (Value / 1000)
• Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
• 0A
• GMT
Modbus Address:
Modbus Format:
• Peak Current: 39048/39049 ( 9888/9889 hex )
• Peak Current Time: 39116/39117/39118 ( 98CC/98CD/98CE hex )
• 32-bit unsigned
• 6 Bytes
Touchscreen Menu Path:
Home → Log → Stop Current Log → Last Peak Stop Current -4
Summary of Contents for Stellar SR55 Series
Page 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Page 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Page 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...